ACH550 E-Clipse Bypass User’s Manual
2-235
Diagnostics
4024
Selected by PAR
1624
START ENABLE 4
VIBRATION
SWITCH
...
LOW SUCTION
PRES
Alarm will occur when
start order is given and
the “RUN Enable” is not
present
Run Enable condition is
not satisfied.
Bad 24v supply
Bad digital input
24 V common is not
tied to Digital input
common on bypass
when using external 24
v supply
Check 24 Volts on
RBCU unit
Check for 24 volts on
respective DI when
condition is satisfied
Check Parameter 0103
For status of digital
input
4025
LOCAL DISABLED
Alarm is displayed if
MODE LOCK (16.29) is
set to AUTO MODE
and the Hand or Off key
is pressed
4026
AUTO DISABLED
This alarm is displayed
if MODE LOCK (1629)
is set to LOCAL MODE
and the Auto key is
pressed.
4027
COMM CONFIG
ERR
Alarm is displayed if the
drive and bypass MAC
addresses are equal or
invalid.
E-Clipse parameters
5002(BP MAC ID) &
5302 (DV MAC ID) are
set to the same value
Change MAC address
to unique values
4028
FBA PAR CONF
Non embedded
fieldbus has detected
an error in Group 51
parameters
Verify Group 51
parameters
4029
DRIVE FAULTED
The drive is faulted.
Reset drive
4030
OVRD2 VFD
Alarm is generated
when override 2 is
active and the drive is
controlling the motor
NA
Check Parameter 0103
and 0104 for digital
input status
4031
OVRD2 STOP
Alarm is generated
when override 2 is
active and both the
bypass and drive
output contactors are
deenergized
NA
Check Parameter 0103
and 0104 for digital
input status
Alarm
Code
Alarm Name In
Panel
Alarm
Possible Cause
Corrective Action
Summary of Contents for ACH550-BCR
Page 4: ...iv Manual contents ...
Page 6: ......
Page 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 36: ...1 32 ACH550 UH User s Manual Installation ...
Page 70: ...1 66 ACH550 UH User s Manual Application macros ...
Page 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Page 348: ......
Page 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Page 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Page 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Page 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Page 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Page 608: ......
Page 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Page 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Page 641: ......