1-132
ACH550-UH User’s Manual
Parameters
Group 31: AUTOMATIC RESET
This group defines conditions for automatic resets. An automatic reset occurs after a
particular fault is detected. The drive holds for a set delay time, then automatically
restarts. You can limit the number of resets in a specified time period and set up
automatic resets for a variety of faults.
Group 31: Automatic Reset
Code Description Range
Resolution
Default
S
3101
NUMBER OF TRIALS
0…5
1
5
Sets the number of allowed automatic resets within a trial period defined by 3102
TRIAL
TIME
.
• If the number of automatic resets exceeds this limit (within the trial time), the drive prevents additional automatic
resets and remains stopped.
• Starting then requires a successful reset performed from the control panel or from a source selected by 1604
FAULT
RESET
SEL
.
Example:
Three faults have occurred in the trial time. The last is reset only if the value for 3101
NUMBER
OF
TRIALS
is
3 or more.
3102
TRIAL TIME
1.0…600.0 s
0.1 s
30.0 s
Sets the time period used for counting and limiting the number of resets.
• See 3101
NUMBER
OF
TRIALS
.
3103
DELAY TIME
0.0…120.0 s
0.1 s
6.0 s
Sets the delay time between a fault detection and attempted drive restart.
• If
DELAY
TIME
= zero, the drive resets immediately.
3104
AR OVERCURRENT
0, 1
1
0 (
DISABLE
)
Sets the automatic reset for the overcurrent function on or off.
0 =
DISABLE
– Disables automatic reset.
1 =
ENABLE
– Enables automatic reset.
• Automatically resets the fault (
OVERCURRENT
) after the delay set by 3103
DELAY
TIME
, and the drive resumes
normal operation.
3105
AR OVERVOLTAGE
0, 1
1
1 (
ENABLE
)
Sets the automatic reset for the overvoltage function on or off.
0 =
DISABLE
– Disables automatic reset.
1 =
ENABLE
– Enables automatic reset.
• Automatically resets the fault (
DC
OVERVOLT
) after the delay set by 3103
DELAY
TIME
, and the drive resumes
normal operation.
3106
AR UNDERVOLTAGE
0, 1
1
1 (
ENABLE
)
Sets the automatic reset for the undervoltage function on or off.
0 =
DISABLE
– Disables automatic reset.
1 =
ENABLE
– Enables automatic reset.
• Automatically resets the fault (
DC
UNDERVOLT
) after the delay set by 3103
DELAY
TIME
, and the drive resumes
normal operation.
3107
AR AI<MIN
0, 1
1
1 (
ENABLE
)
Sets the automatic reset for the analog input less than minimum value function on or off.
0 =
DISABLE
– Disables automatic reset.
1 =
ENABLE
– Enables automatic reset.
• Automatically resets the fault (
AI
<
MIN
) after the delay set by 3103
DELAY
TIME
, and the drive resumes normal
operation.
WARNING!
When the analog input signal is restored, the drive may restart, even after a long stop. Make
sure that automatic, long delayed starts will not cause physical injury and/or damage equipment.
X
X X
Time
Trial time
x = Automatic reset
Summary of Contents for ACH550-BCR
Page 4: ...iv Manual contents ...
Page 6: ......
Page 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 36: ...1 32 ACH550 UH User s Manual Installation ...
Page 70: ...1 66 ACH550 UH User s Manual Application macros ...
Page 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Page 348: ......
Page 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Page 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Page 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Page 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Page 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Page 608: ......
Page 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Page 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Page 641: ......