Parameters
8119
AUTOCHNG LEVEL
0.0…100.0%
0.1%
50.0%
Sets an upper limit, as a percent of output capacity, for the autochange logic. When the output from the PID/PFA
control block exceeds this limit, autochange is prevented. For example, use this parameter to deny autochange
when the Pump-Fan system is operating near maximum capacity.
Autochange overview
The purpose of the autochange operation is to equalize duty time between multiple motors used in a system. At
each autochange operation:
• A different motor takes a turn connected to the ACH550 output – the speed regulated motor.
• The starting order of the other motors rotates.
The Autochange function requires:
• External switchgear for changing the drive’s output power connections.
• Parameter 8120
INTERLOCKS
= value > 0.
Autochange is performed when:
• The running time since the previous autochange reaches the time set by 8118
AUTOCHNG
INTERV
.
• The PFA input is below the level set by this parameter, 8119
AUTOCHNG
LEVEL
.
Note:
The ACH550 always coasts to stop when autochange is performed.
In an autochange, the Autochange function does all of the
following (see the figure):
• Initiates a change when the running time, since the last
autochange, reaches 8118
AUTOCHNG
INTERV
, and PFA
input is below limit 8119
AUTOCHNG
LEVEL
.
• Stops the speed regulated motor.
• Switches off the contactor of the speed regulated motor.
• Increments the starting order counter, to change the
starting order for the motors.
• Identifies the next motor in line to be the speed regulated
motor.
• Switches off the above motor’s contactor, if the motor was
running. Any other running motors are not interrupted.
• Switches on the contactor of the new speed regulated
motor. The autochange switchgear connects this motor to
the ACH550 power output.
• Delays motor start for the time 8122
PFA
START
DELAY
.
• Starts the speed regulated motor.
• Identifies the next constant speed motor in the rotation.
• Switches the above motor on, but only if the new speed
regulated motor had been running (as a constant speed
motor) – This step keeps an equal number of motors running before and after autochange.
• Continues with normal PFA operation.
Starting order counter
The operation of the starting-order counter:
• The relay output parameter definitions (1401…1403 and
1410…1412) establish the initial motor sequence. (The lowest
parameter number with a value 31 (
PFA
) identifies the relay
connected to 1PFA, the first motor, and so on.)
• Initially, 1PFA = speed regulated motor, 2PFA = 1st auxiliary
motor, etc.
• The first autochange shifts the sequence to: 2PFA = speed
regulated motor, 3PFA = 1st auxiliary motor, …, 1PFA = last
auxiliary motor.
• The next autochange shifts the sequence again, and so on.
• If the autochange cannot start a needed motor because all
inactive motors are interlocked, the drive displays an alarm
(2015,
PFA
I
LOCK
).
• When ACH550 power supply is switched off, the counter
preserves the current Autochange rotation positions in permanent memory. When power is restored, the
Autochange rotation starts at the position stored in memory.
• If the PFA relay configuration is changed (or if the PFA enable value is changed), the rotation is reset. (See the
first bullet above.)
Group 81: PFA Control
Code Description Range
Resolution
Default
S
P 8118
B
PID output
P 8119
100%
P 8118
1PFA
2PFA
3PFA
4PFA
4PFA
2PFA
3PFA
A
P 8122
A = Area above 8119
AUTOCHNG
LEVEL
–
autochange not allowed.
B = Autochange occurs.
1PFA, etc. = PID output associated with each motor.
t
No aux
1 aux
motor
2 aux
motors
motors
PID output
P 8119
100%
Output
Area
frequency
Autochange
is allowed
f
MAX
Summary of Contents for ACH550-BCR
Page 4: ...iv Manual contents ...
Page 6: ......
Page 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 36: ...1 32 ACH550 UH User s Manual Installation ...
Page 70: ...1 66 ACH550 UH User s Manual Application macros ...
Page 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Page 348: ......
Page 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Page 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Page 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Page 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Page 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Page 608: ......
Page 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Page 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Page 641: ......