1-210
ACH550-UH User’s Manual
Embedded fieldbus
N2 binary output objects
The following table lists the N2 Binary Output objects defined for the ACH550 drive.
1. N2 LOCAL CTL and N2 LOCAL REF have priority over drive input terminals. Use these binary
outputs for temporary N2 control of the drive when
COMM
is not the selected control source.
DDL file for NCU
The listing below is the Data Definition Language (DDL) file for ACH550 drives used
with the Network Control Units.
This listing is useful when defining drive I/O objects to the Network Controller Units.
Below is the ACH550.DDL file listing.
*******************************************************************
* ABB Drives, ACH 550 Variable Frequency Drive
*******************************************************************
CSMODEL "ACH_550","VND"
AITITLE "Analog_Inputs"
BITITLE "Binary_Inputs"
AOTITLE "Analog_Outputs"
BOTITLE "Binary_Outputs"
N2 Binary Outputs:
Number
Object
Drive Parameter
Range
BO1
STOP/START
Command Word
0 = Stop, 1 = Start to Speed
BO2
FORWARD/REVERSE
Command Word
0 = Forward, 1 = Reverse
BO3
PANEL LOCK
Command Word
0 = Open, 1 = Locked
BO4
RUN ENABLE
Command Word
0 = Enable, 1 = Disable
BO5
REF1/REF2 SELECT
Command Word
0 = Ref1, 1 = Ref2
BO6
FAULT RESET
Command Word
Change 0 -> 1 Resets
BO7
COMMAND RO 1
134 (bit mask 01)
0 = Off, 1 = On
BO8
COMMAND RO 2
134 (bit mask 02)
0 = Off, 1 = On
BO9
COMMAND RO 3
134 (bit mask 04)
0 = Off, 1 = On
BO10
COMMAND RO 4
134 (bit mask 08)
0 = Off, 1 = On
BO11
COMMAND RO 5
134 (bit mask 10)
0 = Off, 1 = On
BO12
COMMAND RO 6
134 (bit mask 20)
0 = Off, 1 = On
BO13
RESET RUN TIME
114 (indirectly)
0 = N/A, 1 = On (Reset Run Time)
BO14
RESET KWH COUNT
115 (indirectly)
0 = N/A, 1 = On (Reset kWh Count)
BO15
PRC PID SELECT
4027 (indirectly)
0 = SET2, 1 = SET2
BO16
N2 LOCAL CTL (Note 1)
Command Word
0 = Auto, 1 = N2
BO17
N2 LOCAL REF (Note 1) Command Word
0 = Auto, 1 = N2
BO18
SAVE PARAMETERS
1607 (indirectly)
0 = N/A, 1 = On (Save Parameters)
BO19
READ MAILBOX
0 = No, 1 = Yes
BO20
WRITE MAILBOX
0 = No, 1 = Yes
Summary of Contents for ACH550-BCR
Page 4: ...iv Manual contents ...
Page 6: ......
Page 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 36: ...1 32 ACH550 UH User s Manual Installation ...
Page 70: ...1 66 ACH550 UH User s Manual Application macros ...
Page 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Page 348: ......
Page 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Page 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Page 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Page 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Page 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Page 608: ......
Page 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Page 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Page 641: ......