ACH550 E-Clipse Bypass User’s Manual
2-95
Embedded fieldbus
Drive relay output control
Using the fieldbus for relay output control requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied reference word(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
1. More than 3 relays requires the addition of a relay extension module.
For example:
To control relays 1 and 2 using serial communication:
Set parameters 1401
RELAY
OUTPUT
1 and 1402
RELAY
OUTPUT
1 = 35 (
COMM
).
Then, for example using N2:
• To turn Relay 1 On: Force object BO7 to On.
• To turn Relay 2 On: Force object BO8 to On.
• To turn both Relay 1 and 2 On: Force objects BO7 and BO8 On.
Note:
Relay status feedback occurs without configuration as defined below.
Drive Parameter
Value
Setting
Protocol Reference
Modbus
N2
FLN
BACnet
ABB
DRV
DCU
PROFILE
1401
RELAY
OUTPUT
1
35
(
COMM
)
Relay Output 1
controlled by fieldbus.
40134 bit 0 or 00033 BO7
40
BO0
1402
RELAY
OUTPUT
2
35
(
COMM
)
Relay Output 2
controlled by fieldbus.
40134 bit 1 or 00034 BO8
41
BO1
1403
RELAY
OUTPUT
3
35
(
COMM
)
Relay Output 3
controlled by fieldbus.
40134 bit 2 or 00035 BO9
42
BO2
1410
1
RELAY
OUTPUT
4
35
(
COMM
)
Relay Output 4
controlled by fieldbus.
40134 bit 3 or 00036 BO10 43
BO3
1411
1
RELAY
OUTPUT
5
35
(
COMM
)
Relay Output 5
controlled by fieldbus.
40134 bit 4 or 00037 BO11 44
BO4
1412
1
RELAY
OUTPUT
6
35
(
COMM
)
Relay Output 6
controlled by fieldbus.
40134 bit 5 or 00038 BO12 45
BO5
Drive
Parameter
Value
Setting
Protocol Reference
Modbus
N2
FLN
BACnet
ABB
DRV
DCU
PROFILE
0122
RO
1-3
STATUS
Relay 1…3
status.
N/A
40122 or 00033...35
BI4…
BI6
76…
78
BI0…
BI2
0123
RO
4-6
STATUS
Relay 4…6
status.
N/A
40123 or 00036...38
BI7…
BI9
79…
81
BI3…
BI5
Summary of Contents for ACH550-BCR
Page 4: ...iv Manual contents ...
Page 6: ......
Page 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 36: ...1 32 ACH550 UH User s Manual Installation ...
Page 70: ...1 66 ACH550 UH User s Manual Application macros ...
Page 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Page 348: ......
Page 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Page 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Page 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Page 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Page 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Page 608: ......
Page 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Page 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Page 641: ......