ACH550-UH User’s Manual
1-153
Parameters
4002
INTEGRATION TIME
0.0…3600.0 s
0.1 s
3.0 s
Defines the PID controller’s integration time.
Integration time is, by definition, the time required to increase the
output by the error value:
• Error value is constant and 100%.
• Gain = 1.
• Integration time of 1 second denotes that a 100% change is
achieved in 1 second.
0.0 =
NOT
SEL
– Disables integration (I-part of controller).
0.1…3600.0 – Integration time (seconds).
• See 4001 for adjustment procedure.
4003
DERIVATION TIME
0.0…10.0 s
0.1 s
0.0 s
Defines the PID controller’s derivation time.
• You can add the derivative of the error to the PID controller
output. The derivative is the error value’s rate of change. For
example, if the process error value changes linearly, the
derivative is a constant added to the PID controller output.
• The error-derivative is filtered with a 1-pole filter. The time
constant of the filter is defined by parameter 4004
PID
DERIV
FILTER
.
0.0…10.0 – Derivation time (seconds).
4004
PID DERIV FILTER
0.0…10.0 s
0.1 s
1.0 s
Defines the filter time constant for the error-derivative part of the PID controller output.
• Before being added to the PID controller output, the error-derivative is filtered with a 1-pole filter.
• Increasing the filter time smooths the error-derivative, reducing noise.
0.0…10.0 – Filter time constant (seconds).
4005
ERROR VALUE INV
0, 1
1
0 (
NO
)
Selects either a normal or inverted relationship between the feedback signal and the drive speed.
0 =
NO
– Normal, a decrease in feedback signal increases drive speed. Error = Ref - Fbk
1 =
YES
– Inverted, a decrease in feedback signal decreases drive speed. Error = Fbk - Ref
4006
UNITS
0…127
1
4 (%)
Selects the unit for the PID controller actual values. (PID1 parameters 0128, 0130 and 0132).
• See parameter 3405 for list of available units.
Group 40: Process PID Set 1
Code Description Range
Resolution
Default
S
P 4002
A
C (P 4001 = 1)
B
A = Error
B = Error value step
C = Controller output with Gain = 1
D = Controller output with Gain = 10
D (P 4001 = 10)
t
100%
Gain
Process error value
P 4003
D-part of controller output
PID output
Error
0%
P 4001
t
t
Summary of Contents for ACH550-UH HVAC
Page 2: ......
Page 8: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 32: ...1 32 ACH550 UH User s Manual Installation ...
Page 66: ...1 66 ACH550 UH User s Manual Application macros ...
Page 186: ...1 186 ACH550 UH User s Manual Parameters ...
Page 333: ...ACH550 UH User s Manual 1 333 Technical data ...