Embedded fieldbus
Miscellaneous driv e control
Using the fieldbus for miscellaneous drive control requires:
•
Drive parameter values set as defined below.
•
Fieldbus controller supplied reference word(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
1. Use Memorize Point command.
Drive
Parameter
Value
Setting
Protocol Reference
Modbus
N2
FLN
BACnet
ABB
DRV
DCU
PROFILE
1601
RUN
ENABLE
7 (
COMM
)
(Not
Recommended)
Run enable by
fieldbus.
40001
bit 3
40031
bit 6
(inverted)
BO4
35
BV12
1604
FAULT
RESET
SEL
8 (
COMM
)
Fault reset by
fieldbus.
40001
bit 7
40031
bit 4
BO6
94
BV14
1606
LOCAL
LOCK
8 (
COMM
)
Source for local
lock selection is
the fieldbus.
Does
not
apply
40031
bit 14
1607
PARAM
SAVE
1 (
SAVE
)
Saves altered
parameters to
memory (then
value returns to
0).
41607
40032
bit 2
BO18
N/A
1
1608
START
ENABLE
1
7 (
COMM
)
(Not
Recommended)
Source for start
enable 1 is the
fieldbus
Command word.
Does
not
apply.
40032
bit 2
BV20
1609
START
ENABLE
2
7 (
COMM
)
(Not
Recommended)
Source for start
enable 2 is the
fieldbus
Command word.
40032
bit 3
BV21
2013
MIN
TORQUE
SEL
7 (
COMM
)
Source for
minimum torque
selection is the
fieldbus.
40031
bit 15
2014
MAX
TORQUE
SEL
7 (
COMM
)
Source for
maximum torque
selection is the
fieldbus.
2201
ACC
/
DEC
1/2
SEL
7 (
COMM
)
Source for ramp
pair selection is
the fieldbus.
40031
bit 10
Summary of Contents for ACH550-UH HVAC
Page 2: ......
Page 8: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 32: ...1 32 ACH550 UH User s Manual Installation ...
Page 66: ...1 66 ACH550 UH User s Manual Application macros ...
Page 186: ...1 186 ACH550 UH User s Manual Parameters ...
Page 333: ...ACH550 UH User s Manual 1 333 Technical data ...