ACH550-UH User’s Manual
1-221
Embedded fieldbus
{23}
LDI
RUN.STOP ACT
STOP
-
1
0
RUN
STOP
{24}
LDO
RUN.STOP CMD
STOP
-
1
0
RUN
STOP
{25}
LDI
EXT1.2 ACT
EXT1
-
1
0
EXT2
EXT1
{26}
LDO
EXT1.2 CMD
EXT1
-
1
0
EXT2
EXT1
{27}
LDI
DRIVE READY
NOTRDY
-
1
0
READY
NOTRDY
{28}
LDI
AT SETPOINT
NO
-
1
0
YES
NO
{29}
LDO
DAY.NIGHT
DAY
-
1
0
NIGHT
DAY
30
LAO
CURRENT LIM
0
A
0.1
0
-
-
31
LAO
ACCEL TIME 1
300
sec
0.1
0
-
-
32
LAO
DECEL TIME 1
300
sec
0.1
0
-
-
{33}
LDI
HANDAUTO
ACT
AUTO
-
1
0
HAND
AUTO
{34}
LDI
ENA.DIS ACT
DISABL
-
1
0
ENABLE
DISABL
{35}
LDO
ENA.DIS CMD
DISABL
-
1
0
ENABLE
DISABL
{36}
LDI
FLN LOC ACT
AUTO
-
1
0
FLN
AUTO
{37}
LDI
FLN CTL SRC
NO
-
1
0
YES
NO
{38}
LDI
FLN REF1 SRC
NO
-
1
0
YES
NO
{39}
LDI
FLN REF2 SRC
NO
-
1
0
YES
NO
{40}
LDO
RO 1
COMMAND
OFF
-
1
0
ON
OFF
{41}
LDO
RO 2
COMMAND
OFF
-
1
0
ON
OFF
{42}
LDO
RO 3
COMMAND
OFF
-
1
0
ON
OFF
{43}
LDO
RO 4
COMMAND
OFF
-
1
0
ON
OFF
{44}
LDO
RO 5
COMMAND
OFF
-
1
0
ON
OFF
{45}
LDO
RO 6
COMMAND
OFF
-
1
0
ON
OFF
{46}
LAO
AO 1
COMMAND
PCT
PCT
0.1
0
-
-
{47}
LAO
AO 2
COMMAND
PCT
PCT
0.1
0
-
-
48
LDO
RST RUN TIME
NO
-
1
0
RESET
NO
49
LDO
RESET KWH
NO
-
1
0
RESET
NO
50
LAO
PRC PID GAIN
10
PCT
0.1
0
-
-
51
LAO
PRC PID ITIM
600
SEC
0.1
0
-
-
52
LAO
PRC PID DTIM
0
SEC
0.1
0
-
-
53
LAO
PRC PID DFIL
10
SEC
0.1
0
-
-
FLN Point Database
Point
Subpoint Name
Factory
Default
Engr.
Units
Slope
Intercept
On Text
Off Text
#
Type
(SI Units)
Summary of Contents for ACH550-UH HVAC
Page 2: ......
Page 8: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 32: ...1 32 ACH550 UH User s Manual Installation ...
Page 66: ...1 66 ACH550 UH User s Manual Application macros ...
Page 186: ...1 186 ACH550 UH User s Manual Parameters ...
Page 333: ...ACH550 UH User s Manual 1 333 Technical data ...