1-246
ACH550-UH User’s Manual
Embedded fieldbus
The following table summarizes the 4xxxx drive control registers 40001…40099 (for
4xxxx registers above 40099, see the drive parameter list, e.g. 40102 is parameter
0102):
Modbus Register
Access
Remarks
4
0001
CONTROL
WORD
R/W
Maps directly to the profile‘
S
CONTROL
WORD
. Supported
only if 5305 = 0 or 2 (ABB Drives profile). Parameter
5319 holds a copy in hex format.
4
0002
Reference 1
R/W
Range = 0…+20000 (scaled to 0…1105
REF
1
MAX
), or
-20000…0 (scaled to 1105
REF
1
MAX
…0).
4
0003
Reference 2
R/W
Range = 0…+10000 (scaled to 0…1108
REF
2
MAX
), or
-10000…0 (scaled to 1108
REF
2
MAX
…0).
4
0004
STATUS
WORD
R
Maps directly to the profile‘
S
STATUS
WORD
. Supported
only if 5305 = 0 or 2 (ABB Drives profile). Parameter
5320 holds a copy in hex format.
4
0005
Actual 1
(select using 5310)
R
By default, stores a copy of 0103
OUTPUT
FREQ
. Use
parameter 5310 to select a different actual value for this
register.
4
0006
Actual 2
(select using 5311)
R
By default, stores a copy of 0104
CURRENT
. Use
parameter 5311 to select a different actual value for this
register.
4
0007
Actual 3
(select using 5312)
R
By default, stores nothing. Use parameter 5312 to
select an actual value for this register.
4
0008
Actual 4
(select by 5313)
R
By default, stores nothing. Use parameter 5313 to
select an actual value for this register.
4
0009
Actual 5
(select using 5314)
R
By default, stores nothing. Use parameter 5314 to
select an actual value for this register.
4
0010
Actual 6
(select using 5315)
R
By default, stores nothing. Use parameter 5315 to
select an actual value for this register.
4
0011
Actual 7
(select using 5316)
R
By default, stores nothing. Use parameter 5316 to
select an actual value for this register.
4
0012
Actual 8
(select using 5317)
R
By default, stores nothing. Use parameter 5317 to
select an actual value for this register.
4
0031
ACH550
CONTROL
WORD
LSW
R/W
Maps directly to the Least Significant Word of the DCU
profile‘s
CONTROL
WORD
. Supported only if 5305 = 1.
See parameter 0301.
4
0032
ACH550
CONTROL
WORD
MSW
R
Maps directly to the Most Significant Word of the DCU
profile‘s
CONTROL
WORD
. Supported only if 5305 = 1.
See parameter 0302.
4
0033
ACH550
STATUS
WORD
LSW
R
Maps directly to the Least Significant Word of the DCU
profile‘s
CONTROL
WORD
. Supported only if 5305 = 1.
See parameter 0303.
4
0034
ACH550
STATUS
WORD
MSW
R
Maps directly to the Most Significant Word of the DCU
profile‘s
CONTROL
WORD
. Supported only if 5305 = 1.
See parameter 0304.
Summary of Contents for ACH550-UH HVAC
Page 2: ......
Page 8: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 32: ...1 32 ACH550 UH User s Manual Installation ...
Page 66: ...1 66 ACH550 UH User s Manual Application macros ...
Page 186: ...1 186 ACH550 UH User s Manual Parameters ...
Page 333: ...ACH550 UH User s Manual 1 333 Technical data ...