ACH550-UH User’s Manual
1-93
Parameters
10 =
COMM
– Assigns the fieldbus Command Word as the source for the start/stop and direction commands.
• Bits 0, 1, 2 of Command Word 1 (parameter 0301) activates the start/stop and direction commands.
• See Fieldbus user’s manual for detailed instructions.
11 =
TIMED
FUNC
1. – Assigns Start/Stop control to Timed Function 1 (Timed Function activated =
START
; Timed
Function de-activated =
STOP
). See
.
12…14 =
TIMED
FUNC
2…4 – Assigns Start/Stop control to Timed Function 2…4. See
TIMED
FUNC
1 above.
1002
EXT2 COMMANDS
0…14
1
1 (
DI
1)
Defines external control location 2 (
EXT
2) – the configuration of start, stop and direction commands.
• See parameter 1001
EXT
1
COMMANDS
above.
1003
DIRECTION 1…3
1
1
(
FORWARD
)
Defines the control of motor rotation direction.
1 =
FORWARD
– Rotation is fixed in the forward direction.
2 =
REVERSE
– Rotation is fixed in the reverse direction.
3 =
REQUEST
– Rotation direction can be changed on command.
Group 10: Start/Stop/Dir
Code Description Range
Resolution
Default
S