ACH550-UH User’s Manual
1-201
Embedded fieldbus
and read. Mailbox can also be used to adjust parameter settings by writing a value to
any parameter identified. The following table describes the use of this function.
1. As noted above, Modbus provides direct access to all parameters using the format: 4 followed by
the parameter number.
Actual value scaling
The scaling of actual values can be protocol dependent. In general, for Actual
Values, scale the feedback integer using the parameter’s resolution. (See
section for parameter resolutions.) For example:
Where parameters are in percent, the
Complete parameter descriptions
section
specifies what parameter corresponds to 100%. In such cases, to convert from
percent to engineering units, multiply by the value of the parameter that defines
100% and divide by 100%. For example:
1. Assuming, for the sake of this example, that the Actual Value uses parameter 9908
MOT
NOM
SPEED
as the 100% reference, and that 9908 = 1500 rpm.
2. Assuming, for the sake of this example, that the Actual Value uses parameter 9907
MOT
NOM
FREQ
as the 100% reference, and that 9907 = 500 Hz.
Although Actual Value scaling could differ from the above for the N2 and FLN
protocols, it currently does not. To confirm, see the following sections, as
appropriate:
•
in the
section.
•
in the
section.
Scaling does not apply for the BACnet protocol.
Name
Description
Protocol Reference
Modbus
1
N2
FLN
BACnet
Mailbox
Parameter
Enter the number of the drive parameter
to access.
Does not
apply.
AO19
95
AV25
Mailbox
Data
Contains the parameter value after a
read, or enter the desired parameter
value for a write.
AO20
96
AV26
Mailbox
Read
A binary value triggers a read – the value
of the “Mailbox Parameter” appears in
“Mailbox data”.
BO19
97
BV15
Mailbox
Write
A binary value triggers a write – the drive
value for the “Mailbox Parameter”
changes to the value in “Mailbox data”.
BO20
98
BV16
Feedback
Integer
Parameter
Resolution
(Feedback Integer) * (Parameter Resolution) = Scaled Value
1
0.1 mA
1 * 0.1 mA = 0.1 mA
10
0.1%
10 * 0.1% = 1%
Feedback
Integer
Parameter
Resolution
Value of the
Parameter that
defines 100%
(Feedback Integer) * (Parameter Resolution) *
(Value of 100% Ref.) / 100% = Scaled Value
10
0.1%
1500 rpm
1
10 * 0.1% * 1500 RPM / 100% = 15 rpm
100
0.1%
500 Hz
2
100 * 0.1% * 500 Hz / 100% = 50 Hz
Summary of Contents for ACH550-UH HVAC
Page 2: ......
Page 8: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 32: ...1 32 ACH550 UH User s Manual Installation ...
Page 66: ...1 66 ACH550 UH User s Manual Application macros ...
Page 186: ...1 186 ACH550 UH User s Manual Parameters ...
Page 333: ...ACH550 UH User s Manual 1 333 Technical data ...