ACH550-UH User’s Manual
1-279
Fieldbus adapter
Generic profile technical data
Overview
The generic profile aims to fulfill the industry-standard drive profile for each protocol
(e.g. PROFIdrive for PROFIBUS, AC/DC Drive for DeviceNet).
Control Word
As described earlier in
CONTROL
WORD
is the principal means
for controlling the drive from a fieldbus system. For specific
CONTROL
WORD
content,
see the user’s manual provided with the FBA module.
Status Word
As described earlier in
, the contents of the
STATUS
WORD
is status
information, sent by the drive to the master station. For specific
STATUS
WORD
content, see the user’s manual provided with the FBA module.
Reference
As described earlier in
, the
REFERENCE
word is a speed or
frequency reference.
Note:
REF
2 is not supported by the Generic Drive profiles.
Reference scaling
REFERENCE
scaling is fieldbus type specific. However, at the drive, the meaning of a
100%
REFERENCE
value is fixed as described in the table below. For a detailed
description on the range and scaling of the
REFERENCE
, see the user’s manual
supplied with the FBA module.
Generic Profile
Reference
Range
Reference
Type
Scaling
Remarks
REF
Fieldbus
specific
Speed
-100% = -
(par. 9908)
0 = 0
+100 =
(par. 9908)
Final reference limited by
1104/1105.
Actual motor speed limited by 2001/
2002 (speed).
Frequency
-100% = -
(par. 9907)
0 = 0
+100 =
(par. 9907)
Final reference limited by
1104/1105.
Actual motor speed limited by 2007/
2008 (frequency).
Summary of Contents for ACH550-UH HVAC
Page 2: ......
Page 8: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 32: ...1 32 ACH550 UH User s Manual Installation ...
Page 66: ...1 66 ACH550 UH User s Manual Application macros ...
Page 186: ...1 186 ACH550 UH User s Manual Parameters ...
Page 333: ...ACH550 UH User s Manual 1 333 Technical data ...