26
ACH580 Installation, Operation and Maintenance Manual
ACH580-01 Installation
Fuses
Note:
The UL listed fuses in the table are the required branch circuit protection.
Fuses are to be provided as part of the installation.
• Fuses are not included in the purchased drive and must be provided by others.
• Fuses with higher current rating than specified must not be used.
• Fuses with lower current rating than specified may be used if they are of the same
class and voltage rating. It is the user's responsibility to verify that lower current
rated fuses are compliant with local regulations and appropriate for the
application.
• Drive fuses must be used to maintain the drive UL listing. Additional protection
can be used. Refer to local codes and regulations.
208...240 volt, fuse requirements
ACH580-01-
Input
curren
t
A
UL
Maximu
m
current
Voltag
e
rating
Bussmann type 1
UL class
3-phase UN = 208 V
04A6-2
4.6
15
600
KTK-R-15 or JJS-15
CC or T
06A6-2
6.6
15
600
KTK-R-15 or JJS-15
CC or T
07A5-2
7.5
15
600
KTK-R-15 or JJS-15
CC or T
10A6-2
10.6
15
600
KTK-R-15 or JJS-15
CC or T
017A-2
16.7
30
600
KTK-R-30 or JJS-30
CC or T
024A-2
24.2
40
600
JJS-40
T
031A-2
30.8
40
600
JJS-40
T
046A-2
46.2
80
600
JJS-80
T
059A-2
59.4
80
600
JJS-80
T
075A-2
74.8
100
600
JJS-100
T
088A-2
88
150
600
JJS-150
T
114A-2
114
150
600
JJS-150
T
144A-2
143
200
600
JJS-200
T
169A-2
169
250
600
JJS-250
T
211A-2
211
300
600
JJS-300
T
273A-2
273
400
600
JJS-400
T
1) ABB does not require Bussmann brand fuses. Fuses which meet the
appropriate UL class type, current rating, and are rated at 600V, 200 kA may be
used.
ACH580_Inst_Op_Maint_Rev G.book Page 26