ACH580 Installation, Operation and Maintenance Manual
75
ACH580-01 Installation
001C
A non-existing
parameter or block is
used in the program.
Edit the program to correct the
parameter reference, or to use an
existing block.
001D
Parameter type invalid
for selected pin.
Edit the program to correct the
parameter reference.
001E
Output to parameter
failed because the
parameter was write-
protected.
Check the parameter reference in the
program.
Check for other sources affecting the
target parameter.
0023
Program file
incompatible with
current firmware
version.
Adapt the program to current block
library and firmware version.
0024
Other
–
Contact your local ABB
representative, quoting the auxiliary
code.
64B1
Internal SSW fault
Internal fault.
Reboot the control unit (using
parameter
96.08 Control board boot
)
or by cycling power. If the problem
persists, contact your local ABB
representative.
64B2
User set fault
Loading of user
parameter set failed
because
• requested set does
not exist
• set is not compatible
with control program
• drive was switched
off during loading.
Ensure that a valid user parameter set
exists. Reload if uncertain.
64E1
Kernel overload
Operating system error. Reboot the control unit (using
parameter
96.08 Control board boot
)
or by cycling power. If the problem
persists, contact your local ABB
representative.
64B1
Fault reset
A fault has been reset.
The cause of the fault
no longer exists and
the fault reset has been
requested and
completed.
Informative fault.
6581
Parameter system
Parameter load or save
failed.
Try forcing a save using parameter
96.07 Parameter save manually
.
Retry.
6591
Backup/Restore timeout
During backup creating
or restoring operation a
panel or PC-tool has
failed to communicate
with the drive as part
this operation.
Check panel or PC-tool
communication and if it is still in
backup or restore state.
Code
(hex)
Fault / Aux. code
Cause
What to do
ACH580_Inst_Op_Maint_Rev G.book Page 75