Make sure that …
The cooling air flows freely in and out of the drive. Air recirculation inside the cabinet is not be possible
(air baffle plates are on place, or there is another air guiding solution).
If the drive is connected to a network other than a symmetrically grounded TN-S system: You have
done all the required modifications (for example, you may need to disconnect the EMC filter or ground-
to-phase varistor). See the electrical installation instructions.
The enclosures of the equipment in the cabinet have proper galvanic connection to the cabinet protective
earth (ground) busbar; The connection surfaces at the fastening points are bare (unpainted) and the
connections are tight, or separate grounding conductors have been installed.
The main circuit connections inside the drive cabinet correspond to the circuit diagrams.
The control unit has been connected. See the circuit diagrams.
Appropriate AC fuses and main disconnecting device are installed.
There is an adequately sized protective earth (ground) conductor(s) between the drive and the
switchboard, the conductor is connected to correct terminal, and the terminal is tightened to the correct
torque.
Proper grounding has also been measured according to the regulations.
The input power cable is connected to the correct terminals, the phase order is correct, and the terminals
are tightened to the correct torque.
There is an adequately sized protective earth (ground) conductor between the motor and the drive,
and the conductor is connected to the correct terminal, and the terminal is tightened to the correct
torque.
Proper grounding has also been measured according to the regulations.
The motor cable is connected to the correct terminals, the phase order is correct, and the terminals
are tightened to the correct torque.
The motor cable is routed away from other cables.
No power factor compensation capacitors are connected to the motor cable.
If an external brake resistor is connected to the drive: There is an adequately sized protective earth
(ground) conductor between the brake resistor and the drive, and the conductor is connected to the
correct terminal, and the terminals are tightened to the correct torque. Proper grounding has also been
measured according to the regulations.
If an external brake resistor is connected to the drive: The brake resistor is connected to the correct
terminals, and the terminals are tightened to the correct torque.
If an external brake resistor is connected to the drive: The brake resistor cable is routed away from
other cables.
The control cables are connected to the correct terminals, and the terminals are tightened to the correct
torque.
If a drive bypass connection will be used: The direct-on-line contactor of the motor and the drive output
contactor are either mechanically and/or electrically interlocked, that is, they cannot be closed at the
same time. A thermal overload device must be used for protection when bypassing the drive. Refer to
local codes and regulations.
There are no tools, foreign objects or dust from drilling inside the drive.
The area in front of the drive is clean: the drive cooling fan cannot draw any dust or dirt inside.
Cover(s) of the motor connection box are in place. Cabinet shrouds are in place and doors are closed.
The motor and the driven equipment are ready for power-up.
120 Installation checklist
Summary of Contents for ACH580-04
Page 1: ... ABB DRIVES FOR HVAC ACH580 04 drive modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 54: ...54 ...
Page 88: ...88 ...
Page 100: ...100 ...
Page 118: ...118 ...
Page 122: ...122 ...
Page 124: ...124 ...
Page 128: ...3 6 5 5 128 Maintenance ...
Page 134: ...134 ...
Page 156: ...R10 standard configuration 156 Dimension drawings ...
Page 157: ...R10 with E208 0H354 H356 H370 0H371 Dimension drawings 157 ...
Page 158: ...R10 with option B051 158 Dimension drawings ...
Page 159: ...R10 with option E208 H356 P906 192 Tools R10 3 1 Dimension drawings 159 ...
Page 160: ...R10 with option E208 0H371 H356 0H354 H370 P906 Tools 191 R10 2 1 160 Dimension drawings ...
Page 161: ...R10 with option B051 P906 190 Tools R10 1 1 Dimension drawings 161 ...
Page 162: ...R11 standard configuration 162 Dimension drawings ...
Page 163: ...R11 with option E208 0H371 H356 0H354 H370 Dimension drawings 163 ...
Page 164: ...R11 with option B051 164 Dimension drawings ...
Page 165: ...R11 with option E208 H356 P906 Dimension drawings 165 ...
Page 166: ...R11 with option E208 0H371 H356 0H354 H370 P906 166 Dimension drawings ...
Page 167: ...R11 with option B051 P906 Dimension drawings 167 ...
Page 186: ... Declaration of conformity 186 The Safe torque off function ...
Page 206: ...Dimension drawing 206 External control unit option P906 ...
Page 212: ...212 ...
Page 224: ...224 ...
Page 226: ...226 ...
Page 234: ...234 ...