Total load capacity of this outputs is 6.0 W (250 mA / 24 V)
minus the power taken by the option modules installed on
board.
Terminal size: 0.14 … 2.5 mm2 (26 … 14 AWG)
+24 V DC output
(Term. 10)
Input type: NPN/PNP
Terminal size: 0.14 … 2.5 mm2 (26 … 14 AWG)
Digital inputs DI1…DI6
(Term. 13…18)
DI1…DI4 (Term. 13…16)
12/24 V DC logic levels: "0" < 4 V, "1" > 8 V
Rin: 3 kohm
Hardware filtering: 0.04 ms, digital filtering: 2 ms sampling
DI5 (Term.17)
Can be used as a digital or frequency input.
12/24 V DC logic levels: "0" < 4 V, "1" > 8 V
Rin: 3 kohm
Max. frequency: 16 kHz
Symmetrical signal (duty cycle D = 0.50)
DI6 (Term.18)
Can be used as a digital or PTC input.
12/24 V DC logic levels: "0" < 3 V, "1" > 8 V
Rin: 3 kohm
Max. frequency: 16 kHz
Symmetrical signal (duty cycle D = 0.50)
Hardware filtering: 0.04 ms, digital filtering: 2 ms sampling
Note: DI6 is not supported in the NPN configuration.
PTC mode – PTC thermistor can be connected between DI6 and
+24 V DC: < 1.5 kohm = ‘1’ (low temperature), > 4 kohm = ‘0’
(high temperature), open circuit = ‘0’ (high temperature).
DI6 is not a reinforced/double insulated input. Connecting the
motor PTC sensor to this input requires usage of a rein-
forced/double insulated PTC sensor inside the motor
250 V AC / 30 V DC, 2 A. Terminal size: 0.14 … 2.5 mm2 (26 …
14 AWG)
Relay outputs RO1…RO3
(Term. 19…27)
See section
.
Current/voltage input mode selected with a parameter, see
and AI2 as Pt100, Pt1000, Ni1000, KTY83 and KTY84 sensor in-
puts (X1) (page 141)
Current input: 0(4)…20 mA,
Rin: 100 ohm
Voltage input: 0(2)…10 V,
Rin: > 200 kohm
Terminal size: 0.14 … 2.5 mm2 (26 … 14 AWG)
Analog inputs AI1 and AI2
(Term. 2 and 5)
Inaccuracy: typical ±1%, max. ±1.5% of full scale
Inaccuracy for Pt100 sensors: 10 °C (50 °F)
Control unit 143
Summary of Contents for ACH580-31
Page 1: ... ABB INDUSTRIAL DRIVES ACH580 31 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 30: ...30 ...
Page 39: ...Operation principle 39 ...
Page 56: ...56 ...
Page 90: ...90 ...
Page 112: ...R3 1 7 N m 112 Electrical installation IEC ...
Page 113: ...R6 1 7 N m Electrical installation IEC 113 ...
Page 114: ...R8 1 7 N m 114 Electrical installation IEC ...
Page 130: ...R3 Max 250 mA 130 Electrical installation North America NEC ...
Page 131: ...R6 Electrical installation North America NEC 131 ...
Page 150: ...150 ...
Page 152: ...152 ...
Page 166: ... Fan arrow must point up 166 Maintenance ...
Page 212: ...212 ...
Page 214: ...R3 IP21 UL Type 1 3AXD50000028643 214 Dimension drawings ...
Page 215: ...R3 Option B056 IP55 UL Type 12 3AXD50000045321 Dimension drawings 215 ...
Page 216: ...R6 IP21 UL Type 1 3AXD50000037446 216 Dimension drawings ...
Page 217: ...R6 Option B056 IP55 UL Type 12 3AXD50000045351 Dimension drawings 217 ...
Page 218: ...R8 IP21 UL Type 1 3AXD50000147052 218 Dimension drawings ...
Page 219: ...R8 Option B056 IP55 UL Type 12 3AXD50000147052 Dimension drawings 219 ...
Page 220: ...220 ...
Page 242: ...242 ...
Page 250: ...250 ...
Page 254: ...254 ...
Page 262: ...262 ...
Page 268: ...268 ...
Page 275: ...CMOD 01 multifunction extension module external 24 V AC DC and digital I O 275 ...
Page 276: ...276 ...
Page 282: ...282 CMOD 02 multifunction extension module external 24 V AC DC and isolated PTC interface ...