UL (one fuse per phase)
Input current
ACH580-
31-…
UL class
Bussmann
type
Voltage rating
Nominal cur-
rent
V
A
A
T
JJS-225
600
225
134
156A-4
T
JJS-300
600
300
163
180A-4
3-phase
Un = 480 V
T
JJS-15
600
15
7.0
09A5-4
T
JJS-20
600
20
9.0
12A7-4
T
JJS-25
600
25
12.0
018A-4
T
JJS-35
600
35
17.0
026A-4
T
JJS-40
600
40
24
033A-4
T
JJS-50
600
50
29
039A-4
T
JJS-60
600
60
34
046A-4
T
JJS-80
600
80
44
062A-4
T
JJS-90
600
90
54
073A-4
T
JJS-110
600
110
66
088A-4
T
JJS-150
600
150
82
106A-4
T
JJS-200
600
200
111
145A-4
T
JJS-225
600
225
134
169A-4
T
JJS-300
600
300
163
206A-4
1.
Fuses are required as part of the installation, are not included in the base drive
configuration and must be provided by others.
2.
Fuses with a higher current rating than specified must not be used.
3.
The UL listed fuses recommended by ABB are the required branch circuit
protection per NEC. Circuit breakers listed in section Circuit breakers (UL) are
also acceptable as branch circuit protection.
4. The recommended size or smaller UL listed 248 fast acting, time delay, or high
speed fuses must be used to maintain the UL listing of the drive. Additional
protection can be used. Refer to local codes and regulations.
5. A fuse of a different class can be used at the high fault rating where the
I
peak
and
I
2
t of the new fuse is not greater than that of the specified fuse.
6. UL listed 248 fast acting, time delay, or high speed fuses from other
manufacturers can be used if they meet the same class and rating requirements
specified in the rules above.
7.
When installing a drive, always follow ABB installation instructions, NEC
requirements and local codes.
8. Alternative fuses can be used if they meet certain characteristics. For
acceptable fuses, see the manual supplement (
Technical data 183
Summary of Contents for ACH580-31
Page 1: ... ABB INDUSTRIAL DRIVES ACH580 31 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 30: ...30 ...
Page 39: ...Operation principle 39 ...
Page 56: ...56 ...
Page 90: ...90 ...
Page 112: ...R3 1 7 N m 112 Electrical installation IEC ...
Page 113: ...R6 1 7 N m Electrical installation IEC 113 ...
Page 114: ...R8 1 7 N m 114 Electrical installation IEC ...
Page 130: ...R3 Max 250 mA 130 Electrical installation North America NEC ...
Page 131: ...R6 Electrical installation North America NEC 131 ...
Page 150: ...150 ...
Page 152: ...152 ...
Page 166: ... Fan arrow must point up 166 Maintenance ...
Page 212: ...212 ...
Page 214: ...R3 IP21 UL Type 1 3AXD50000028643 214 Dimension drawings ...
Page 215: ...R3 Option B056 IP55 UL Type 12 3AXD50000045321 Dimension drawings 215 ...
Page 216: ...R6 IP21 UL Type 1 3AXD50000037446 216 Dimension drawings ...
Page 217: ...R6 Option B056 IP55 UL Type 12 3AXD50000045351 Dimension drawings 217 ...
Page 218: ...R8 IP21 UL Type 1 3AXD50000147052 218 Dimension drawings ...
Page 219: ...R8 Option B056 IP55 UL Type 12 3AXD50000147052 Dimension drawings 219 ...
Page 220: ...220 ...
Page 242: ...242 ...
Page 250: ...250 ...
Page 254: ...254 ...
Page 262: ...262 ...
Page 268: ...268 ...
Page 275: ...CMOD 01 multifunction extension module external 24 V AC DC and digital I O 275 ...
Page 276: ...276 ...
Page 282: ...282 CMOD 02 multifunction extension module external 24 V AC DC and isolated PTC interface ...