Note: Circuit breakers are not yet validated as protection device for R6 frame “HW
V2”. R6 frame “HW V2” variants must use fuses. “HW V2” is shown in the type
designation label.
Max.
I
peak
Max.
I
2
t
ABB circuit breaker
Drive
volume
CB
Voltage
CB
Maxim-
um cur-
rent
Input
current
Frame
ACH580-
31-…
kA
A
2
s
65kA @ 480V
in
3
V
A
A
3-phase
U
n
= 480 V
23.2
0.512×10
6
XT2Hαβ020#********
1638
480
20
7.0
R3
07A6-4
23.2
0.512×10
6
XT2Hαβ020#********
1638
480
20
9.0
R3
012A-4
23.2
0.512×10
6
XT2Hαβ035#********
1638
480
35
12.0
R3
014A-4
23.2
0.512×10
6
XT2Hαβ035#********
1638
480
35
17.0
R3
023A-4
23.2
0.512×10
6
XT2Hαβ070#********
3507
480
70
24
R6
027A-4
23.2
0.512×10
6
XT2Hαβ070#********
3507
480
70
29
R6
034A-4
23.2
0.512×10
6
XT2Hαβ070#********
3507
480
70
34
R6
044A-4
23.2
0.512×10
6
XT2Hαβ125#********
3507
480
125
44
R6
052A-4
23.2
0.512×10
6
XT2Hαβ125#********
3507
480
125
54
R6
065A-4
23.2
0.512×10
6
XT2Hαβ125#********
3507
480
125
66
R6
077A-4
30
0.98×10
6
XT4Hαβ225#********
6602
480
225
82
R8
096A-4
30
0.98×10
6
XT4Hαβ225#********
6602
480
225
111
R8
124A-4
30
0.98×10
6
XT4Hαβ250#********
6602
480
250
134
R8
156A-4
30
0.98×10
6
XT4Hαβ250#********
6602
480
250
163
R8
180A-4
Notes:
1.
Drives that have an enclosure minimum volume listed must be mounted in an
enclosure ≥ enclosure minimum volume specified in the tables above.
2.
When multiple drives that have an enclosure minimum volume specified are
installed in the same enclosure, minimum volume of the enclosure is determined
by largest enclosure minimum volume of the drives to be placed in the
enclosure, plus the volume(s) of each additional drive. i.e. for the 480V R6 and
R3 drive select enclosure with the volume ≥ 16200+1011 = 17211 in
3
.
3.
For UL Open Type, UL Type 1 or UL Type 12 drives that have a minimum
enclosure volume indicated with ¤, no minimum enclosure volume is required
but the drive must be mounted inside an enclosure.
4. If combining a drive with an enclosure minimum volume specified and others
with an enclosure minimum volume indicated with ¤, start with the largest
specified enclosure minimum volume listed and add the drive volumes for the
other drives.
186 Technical data
Summary of Contents for ACH580-31
Page 1: ... ABB INDUSTRIAL DRIVES ACH580 31 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 30: ...30 ...
Page 39: ...Operation principle 39 ...
Page 56: ...56 ...
Page 90: ...90 ...
Page 112: ...R3 1 7 N m 112 Electrical installation IEC ...
Page 113: ...R6 1 7 N m Electrical installation IEC 113 ...
Page 114: ...R8 1 7 N m 114 Electrical installation IEC ...
Page 130: ...R3 Max 250 mA 130 Electrical installation North America NEC ...
Page 131: ...R6 Electrical installation North America NEC 131 ...
Page 150: ...150 ...
Page 152: ...152 ...
Page 166: ... Fan arrow must point up 166 Maintenance ...
Page 212: ...212 ...
Page 214: ...R3 IP21 UL Type 1 3AXD50000028643 214 Dimension drawings ...
Page 215: ...R3 Option B056 IP55 UL Type 12 3AXD50000045321 Dimension drawings 215 ...
Page 216: ...R6 IP21 UL Type 1 3AXD50000037446 216 Dimension drawings ...
Page 217: ...R6 Option B056 IP55 UL Type 12 3AXD50000045351 Dimension drawings 217 ...
Page 218: ...R8 IP21 UL Type 1 3AXD50000147052 218 Dimension drawings ...
Page 219: ...R8 Option B056 IP55 UL Type 12 3AXD50000147052 Dimension drawings 219 ...
Page 220: ...220 ...
Page 242: ...242 ...
Page 250: ...250 ...
Page 254: ...254 ...
Page 262: ...262 ...
Page 268: ...268 ...
Page 275: ...CMOD 01 multifunction extension module external 24 V AC DC and digital I O 275 ...
Page 276: ...276 ...
Page 282: ...282 CMOD 02 multifunction extension module external 24 V AC DC and isolated PTC interface ...