UL (NEC)3)
IEC1)
Frame
size
ACH580-
31-…
Cu cable type
Al cable type 2)
Cu cable type
AWG/kcmil
mm2
mm2
2
3×50
3×35
R6
065A-4
2
3×50
3×35
R6
077A-4
1/0
3×70
3×50
R8
096A-4
2/0
3×95
3×70
R8
124A-4
4/0
3×150
3×95
R8
156A-4
250 MCM
3×185
3×120
R8
180A-4
1) The cable sizing is based on max. 9 cables laid on a cable ladder side by side,
three ladder type trays one on top of the other, ambient temperature 30 °C, PVC
insulation, surface temperature 70 °C (EN 60204-1 and IEC 60364-5-52/2001). For
other conditions, size the cables according to local safety regulations, appropriate
input voltage and the load current of the drive.
2) Aluminum cables must not be used with drives of frame size R3.
3) The cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F)
wire insulation at 40 °C (104 °F) ambient temperature. Not more than three
current-carrying conductors in raceway or cable or earth (directly buried). For other
conditions, size the cables according to local safety regulations, appropriate input
voltage and the load current of the drive.
4) In the USA, aluminum cables must not be used.
Temperature: For IEC, select a cable rated for at least 70 °C maximum permissible
temperature of conductor in continuous use. For North America, power cables
must be rated for 75 °C (167 °F) or higher.
For surrounding air temperatures above 40 °C (104 °F) or frame R6 with option
+B056 (UL Type 12), select a cable rated for at least 90 °C (194 °F) maximum
permissible temperature of conductor in continuous use.
Voltage: 600 V AC cable is accepted for up to 500 V AC.
Technical data 197
Summary of Contents for ACH580-31
Page 1: ... ABB INDUSTRIAL DRIVES ACH580 31 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 30: ...30 ...
Page 39: ...Operation principle 39 ...
Page 56: ...56 ...
Page 90: ...90 ...
Page 112: ...R3 1 7 N m 112 Electrical installation IEC ...
Page 113: ...R6 1 7 N m Electrical installation IEC 113 ...
Page 114: ...R8 1 7 N m 114 Electrical installation IEC ...
Page 130: ...R3 Max 250 mA 130 Electrical installation North America NEC ...
Page 131: ...R6 Electrical installation North America NEC 131 ...
Page 150: ...150 ...
Page 152: ...152 ...
Page 166: ... Fan arrow must point up 166 Maintenance ...
Page 212: ...212 ...
Page 214: ...R3 IP21 UL Type 1 3AXD50000028643 214 Dimension drawings ...
Page 215: ...R3 Option B056 IP55 UL Type 12 3AXD50000045321 Dimension drawings 215 ...
Page 216: ...R6 IP21 UL Type 1 3AXD50000037446 216 Dimension drawings ...
Page 217: ...R6 Option B056 IP55 UL Type 12 3AXD50000045351 Dimension drawings 217 ...
Page 218: ...R8 IP21 UL Type 1 3AXD50000147052 218 Dimension drawings ...
Page 219: ...R8 Option B056 IP55 UL Type 12 3AXD50000147052 Dimension drawings 219 ...
Page 220: ...220 ...
Page 242: ...242 ...
Page 250: ...250 ...
Page 254: ...254 ...
Page 262: ...262 ...
Page 268: ...268 ...
Page 275: ...CMOD 01 multifunction extension module external 24 V AC DC and digital I O 275 ...
Page 276: ...276 ...
Page 282: ...282 CMOD 02 multifunction extension module external 24 V AC DC and isolated PTC interface ...