Note: Note: Do not install a drive with the internal EMC filter connected to a system
that the filter is not suitable for. This can cause danger, or damage the drive.
Note: Do not install a drive with the ground-to-phase varistor connected to a
system that the varistor is not suitable for. If you do, the varistor circuit can be
damaged.
If you install the drive to any other system than symmetrically grounded TN-S
system, you may need to disconnect the EMC filter or the ground-to-phase varistor.
See
Grounding system compatibility check (page 93)
■
Category C3
The drive complies with the standard with the following provisions:
•
The motor and control cables are selected as specified in this manual.
•
The drive is installed according to the instructions given in this manual.
•
For the maximum motor cable length with 4 kHz switching frequency, see
section
Motor connection data (page 200)
WARNING! A drive of category C3 is not intended to be used on a low-voltage
public network which supplies domestic premises. Radio frequency
interference is expected if the drive is used on such a network.
Note: Do not install a drive with the integrated EMC filter connected to a system
that the filter is not suitable for. This can cause danger, or damage the drive.
Note: Do not install a drive with the ground-to-phase varistor connected to a
system that the varistor is not suitable for. If you do, the varistor circuit can be
damaged.
■
Category C4
The drive complies with the C4 category with these provisions:
1.
It is made sure that no excessive emission is propagated to neighboring
low-voltage networks. In some cases, the natural suppression in transformers
and cables is sufficient. If in doubt, a supply transformer with static screening
between the primary and secondary windings can be used.
208 Technical data
Summary of Contents for ACH580-31
Page 1: ... ABB INDUSTRIAL DRIVES ACH580 31 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 30: ...30 ...
Page 39: ...Operation principle 39 ...
Page 56: ...56 ...
Page 90: ...90 ...
Page 112: ...R3 1 7 N m 112 Electrical installation IEC ...
Page 113: ...R6 1 7 N m Electrical installation IEC 113 ...
Page 114: ...R8 1 7 N m 114 Electrical installation IEC ...
Page 130: ...R3 Max 250 mA 130 Electrical installation North America NEC ...
Page 131: ...R6 Electrical installation North America NEC 131 ...
Page 150: ...150 ...
Page 152: ...152 ...
Page 166: ... Fan arrow must point up 166 Maintenance ...
Page 212: ...212 ...
Page 214: ...R3 IP21 UL Type 1 3AXD50000028643 214 Dimension drawings ...
Page 215: ...R3 Option B056 IP55 UL Type 12 3AXD50000045321 Dimension drawings 215 ...
Page 216: ...R6 IP21 UL Type 1 3AXD50000037446 216 Dimension drawings ...
Page 217: ...R6 Option B056 IP55 UL Type 12 3AXD50000045351 Dimension drawings 217 ...
Page 218: ...R8 IP21 UL Type 1 3AXD50000147052 218 Dimension drawings ...
Page 219: ...R8 Option B056 IP55 UL Type 12 3AXD50000147052 Dimension drawings 219 ...
Page 220: ...220 ...
Page 242: ...242 ...
Page 250: ...250 ...
Page 254: ...254 ...
Page 262: ...262 ...
Page 268: ...268 ...
Page 275: ...CMOD 01 multifunction extension module external 24 V AC DC and digital I O 275 ...
Page 276: ...276 ...
Page 282: ...282 CMOD 02 multifunction extension module external 24 V AC DC and isolated PTC interface ...