Start-up including validation test
To ensure the safe operation of a safety function, validation is required. The final
assembler of the machine must validate the function by performing a validation
test. The test must be performed
1.
at initial start-up of the safety function
2.
after any changes related to the safety function (circuit boards, wiring,
components, settings, replacement of inverter module, etc.)
3.
after any maintenance work related to the safety function
4. after a drive firmware update
5. at the proof test of the safety function.
■
Competence
The validation test of the safety function must be carried out by a competent
person with adequate expertise and knowledge of the safety function as well as
functional safety, as required by IEC 61508-1 clause 6. The test procedures and
report must be documented and signed by this person.
■
Validation test reports
Signed validation test reports must be stored in the logbook of the machine. The
report shall include documentation of start-up activities and test results, references
to failure reports and resolution of failures. Any new validation tests performed
due to changes or maintenance shall be logged into the logbook.
■
Validation test procedure
After wiring the Safe torque off function, validate its operation as follows.
Note: If a CPTC-02 or an FSPS-21 module is installed, refer to its documentation.
Action
WARNING!
Obey the safety instructions. If you ignore them, injury or death, or damage to
the equipment can occur.
Make sure that the motor can be run and stopped freely during start-up.
Stop the drive (if running), switch the input power off and isolate the drive from the
power line using a disconnector.
Check the STO circuit connections against the wiring diagram.
Close the disconnector and switch the power on.
230 The Safe torque off function
Summary of Contents for ACH580-31
Page 1: ... ABB INDUSTRIAL DRIVES ACH580 31 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 30: ...30 ...
Page 39: ...Operation principle 39 ...
Page 56: ...56 ...
Page 90: ...90 ...
Page 112: ...R3 1 7 N m 112 Electrical installation IEC ...
Page 113: ...R6 1 7 N m Electrical installation IEC 113 ...
Page 114: ...R8 1 7 N m 114 Electrical installation IEC ...
Page 130: ...R3 Max 250 mA 130 Electrical installation North America NEC ...
Page 131: ...R6 Electrical installation North America NEC 131 ...
Page 150: ...150 ...
Page 152: ...152 ...
Page 166: ... Fan arrow must point up 166 Maintenance ...
Page 212: ...212 ...
Page 214: ...R3 IP21 UL Type 1 3AXD50000028643 214 Dimension drawings ...
Page 215: ...R3 Option B056 IP55 UL Type 12 3AXD50000045321 Dimension drawings 215 ...
Page 216: ...R6 IP21 UL Type 1 3AXD50000037446 216 Dimension drawings ...
Page 217: ...R6 Option B056 IP55 UL Type 12 3AXD50000045351 Dimension drawings 217 ...
Page 218: ...R8 IP21 UL Type 1 3AXD50000147052 218 Dimension drawings ...
Page 219: ...R8 Option B056 IP55 UL Type 12 3AXD50000147052 Dimension drawings 219 ...
Page 220: ...220 ...
Page 242: ...242 ...
Page 250: ...250 ...
Page 254: ...254 ...
Page 262: ...262 ...
Page 268: ...268 ...
Page 275: ...CMOD 01 multifunction extension module external 24 V AC DC and digital I O 275 ...
Page 276: ...276 ...
Page 282: ...282 CMOD 02 multifunction extension module external 24 V AC DC and isolated PTC interface ...