Make sure that the power factor compensation unit is suitable for use in
systems with AC drives, ie, harmonic generating loads. In such systems, the
compensation unit should typically be equipped with a blocking reactor or
harmonic filter.
Using a safety switch between the drive and the motor
ABB recommends to install a safety switch between the permanent magnet motor
and the drive output. The switch is needed to isolate the motor from the drive
during maintenance work on the drive.
Implementing an ATEX-certified motor thermal protection
With Q971, the drive provides ATEX-certified safe motor disconnection
without contactor using the drive Safe torque off function. To implement the
thermal protection of a motor in explosive atmosphere (Ex motor), you must also:
•
use an ATEX-certified Ex motor
•
order an ATEX-certified thermistor protection module for the drive (option
+L537), or acquire and install an ATEX-compliant protection relay
•
do the necessary connections.
For more information, see:
Manual code
(English)
User's manual
CPTC-02 ATEX-certified thermistor protection module, Ex II (2) GD (option
+L537+Q971) user's manual
Controlling a contactor between drive and motor
The control of the output contactor depends on how you use the drive, that is,
which motor control mode and which motor stop mode you select.
If you have the vector control mode and motor ramp stop selected, open the
contactor as follows:
1.
Give a stop command to the drive.
2.
Wait until the drive decelerates the motor to zero speed.
3.
Open the contactor.
If you have the vector control mode and motor coast stop selected, or scalar control
mode selected, open the contactor as follows:
1.
Give a stop command to the drive.
2.
Open the contactor.
84 Guidelines for planning the electrical installation
Summary of Contents for ACH580-31
Page 1: ... ABB INDUSTRIAL DRIVES ACH580 31 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 30: ...30 ...
Page 39: ...Operation principle 39 ...
Page 56: ...56 ...
Page 90: ...90 ...
Page 112: ...R3 1 7 N m 112 Electrical installation IEC ...
Page 113: ...R6 1 7 N m Electrical installation IEC 113 ...
Page 114: ...R8 1 7 N m 114 Electrical installation IEC ...
Page 130: ...R3 Max 250 mA 130 Electrical installation North America NEC ...
Page 131: ...R6 Electrical installation North America NEC 131 ...
Page 150: ...150 ...
Page 152: ...152 ...
Page 166: ... Fan arrow must point up 166 Maintenance ...
Page 212: ...212 ...
Page 214: ...R3 IP21 UL Type 1 3AXD50000028643 214 Dimension drawings ...
Page 215: ...R3 Option B056 IP55 UL Type 12 3AXD50000045321 Dimension drawings 215 ...
Page 216: ...R6 IP21 UL Type 1 3AXD50000037446 216 Dimension drawings ...
Page 217: ...R6 Option B056 IP55 UL Type 12 3AXD50000045351 Dimension drawings 217 ...
Page 218: ...R8 IP21 UL Type 1 3AXD50000147052 218 Dimension drawings ...
Page 219: ...R8 Option B056 IP55 UL Type 12 3AXD50000147052 Dimension drawings 219 ...
Page 220: ...220 ...
Page 242: ...242 ...
Page 250: ...250 ...
Page 254: ...254 ...
Page 262: ...262 ...
Page 268: ...268 ...
Page 275: ...CMOD 01 multifunction extension module external 24 V AC DC and digital I O 275 ...
Page 276: ...276 ...
Page 282: ...282 CMOD 02 multifunction extension module external 24 V AC DC and isolated PTC interface ...