Identifying the grounding system of the electrical power network
WARNING!
Only a qualified electrical professional may do the work instructed in this
section. Depending on the installation site, the work may even be categorized
as live working. Continue only if you are an electrical professional certified
for the work. Obey the local regulations. If you ignore them, injury or death
can occur.
To identify the grounding system, examine the supply transformer connection.
See the applicable electrical diagrams of the building. If that is not possible,
measure these voltages at the distribution board, and use the table to define the
grounding system type.
1.
input voltage line to line (U
L-L
)
2.
input voltage line 1 to ground (U
L1-G
)
3.
input voltage line 2 to ground (U
L2-G
)
4. input voltage line 3 to ground (U
L3-G
).
The table below shows the line-to-ground voltages in relation to the line-to-line
voltage for each grounding system.
Electrical power system type
UL3-G
UL2-G
UL1-G
UL-L
Symmetrically grounded TN system (TN-
S system)
0.58·X
0.58·X
0.58·X
X
Corner-grounded delta system (nonsym-
metrical)
0
1.0·X
1.0·X
X
Midpoint-grounded delta system (non-
symmetrical)
0.5·X
0.5·X
0.866·X
X
IT systems (ungrounded or high-resist-
ance-grounded [>30 ohms]) nonsymmet-
rical
Varying level
versus time
Varying level
versus time
Varying level
versus time
X
TT system (the protective earth connec-
tion for the consumer is provided by a
local earth electrode, and there is anoth-
er independently installed at the gener-
ator)
Varying level
versus time
Varying level
versus time
Varying level
versus time
X
Electrical installation – IEC 97
Summary of Contents for ACH580-31
Page 1: ... ABB INDUSTRIAL DRIVES ACH580 31 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 30: ...30 ...
Page 39: ...Operation principle 39 ...
Page 56: ...56 ...
Page 90: ...90 ...
Page 112: ...R3 1 7 N m 112 Electrical installation IEC ...
Page 113: ...R6 1 7 N m Electrical installation IEC 113 ...
Page 114: ...R8 1 7 N m 114 Electrical installation IEC ...
Page 130: ...R3 Max 250 mA 130 Electrical installation North America NEC ...
Page 131: ...R6 Electrical installation North America NEC 131 ...
Page 150: ...150 ...
Page 152: ...152 ...
Page 166: ... Fan arrow must point up 166 Maintenance ...
Page 212: ...212 ...
Page 214: ...R3 IP21 UL Type 1 3AXD50000028643 214 Dimension drawings ...
Page 215: ...R3 Option B056 IP55 UL Type 12 3AXD50000045321 Dimension drawings 215 ...
Page 216: ...R6 IP21 UL Type 1 3AXD50000037446 216 Dimension drawings ...
Page 217: ...R6 Option B056 IP55 UL Type 12 3AXD50000045351 Dimension drawings 217 ...
Page 218: ...R8 IP21 UL Type 1 3AXD50000147052 218 Dimension drawings ...
Page 219: ...R8 Option B056 IP55 UL Type 12 3AXD50000147052 Dimension drawings 219 ...
Page 220: ...220 ...
Page 242: ...242 ...
Page 250: ...250 ...
Page 254: ...254 ...
Page 262: ...262 ...
Page 268: ...268 ...
Page 275: ...CMOD 01 multifunction extension module external 24 V AC DC and digital I O 275 ...
Page 276: ...276 ...
Page 282: ...282 CMOD 02 multifunction extension module external 24 V AC DC and isolated PTC interface ...