Output ratings
App.
power
Max. cur-
rent
Input
rating1)
Frame
size
ACH580-
31-…
Heavy duty-use
Light-duty use
PHd
IHd
PLd
ILd
Sn
Imax
I1
hp
A
hp
A
kVA
A
A
5
7.6
7.5
12
10.0
15.0
9.0
R3
012A-4
7.5
12.0
10
14
11.6
20.4
12.0
R3
014A-4
10
14.0
15
23
19.1
28.8
17.0
R3
023A-4
15
23
20
27
22.4
39.1
24
R6
027A-4
20
27
25
34
28.3
45.9
29
R6
034A-4
25
34
30
44
36.6
57.8
34
R6
044A-4
30
44
40
52
43.2
74.8
44
R6
052A-4
40
52
50
65
54.0
88.4
54
R6
065A-4
50
65
60
77
64.0
110.5
66
R6
077A-4
60
77
75
96
79.8
130.9
82
R8
096A-4
75
96
100
124
103.1
163.2
111
R8
124A-4
100
124
125
156
129.7
210.8
134
R8
156A-4
125
156
150
180
149.6
265.2
163
R8
180A-4
1)
When the DC voltage is boosted, the drive can be drawing more input current
than what is shown on the type designation label. This is the case when the motor
is running continuously at or near the field weakening area and the drive is running
at or near nominal load. It can be a result of certain combinations of DC voltage
boost levels and drive-type-specific derating curves.
The rise in input current can heat the input cable and fuses. To avoid heating, select
an input cable and fuses according to the increased input current caused by the
DC voltage boost. For more information, refer to
ACH580-34 and ACQ580-34 drives product note on DC voltage boost
(3AXD50000769407 [English])
■
Definitions
Nominal input voltage of the drive. For input voltage range, see section
power network specification (page 198)
. 50 Hz for IEC ratings, 60 Hz for UL (NEC)
ratings.
Un
Nominal input current (rms) at 40 °C (104 °F). Continuous rms input current (for
dimensioning cables and fuses).
I1
Nominal output current (available continuously with no overload)
I2
Maximum output current. Available for two seconds at start. Then as long as al-
lowed by drive temperature.
Imax
Typical motor power (no overload). The kilowatt ratings apply to most IEC 4-pole
motors. The horsepower ratings apply to most NEMA 4-pole motors.
Pn
Maximum current with 10% overload, allowed for one minute every ten minutes
when parameter 97.02 Minimum switching frequency is set to 2 kHz or less
ILd
Technical data 171
Summary of Contents for ACH580-31
Page 1: ... ABB INDUSTRIAL DRIVES ACH580 31 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 30: ...30 ...
Page 39: ...Operation principle 39 ...
Page 56: ...56 ...
Page 90: ...90 ...
Page 112: ...R3 1 7 N m 112 Electrical installation IEC ...
Page 113: ...R6 1 7 N m Electrical installation IEC 113 ...
Page 114: ...R8 1 7 N m 114 Electrical installation IEC ...
Page 130: ...R3 Max 250 mA 130 Electrical installation North America NEC ...
Page 131: ...R6 Electrical installation North America NEC 131 ...
Page 150: ...150 ...
Page 152: ...152 ...
Page 166: ... Fan arrow must point up 166 Maintenance ...
Page 212: ...212 ...
Page 214: ...R3 IP21 UL Type 1 3AXD50000028643 214 Dimension drawings ...
Page 215: ...R3 Option B056 IP55 UL Type 12 3AXD50000045321 Dimension drawings 215 ...
Page 216: ...R6 IP21 UL Type 1 3AXD50000037446 216 Dimension drawings ...
Page 217: ...R6 Option B056 IP55 UL Type 12 3AXD50000045351 Dimension drawings 217 ...
Page 218: ...R8 IP21 UL Type 1 3AXD50000147052 218 Dimension drawings ...
Page 219: ...R8 Option B056 IP55 UL Type 12 3AXD50000147052 Dimension drawings 219 ...
Page 220: ...220 ...
Page 242: ...242 ...
Page 250: ...250 ...
Page 254: ...254 ...
Page 262: ...262 ...
Page 268: ...268 ...
Page 275: ...CMOD 01 multifunction extension module external 24 V AC DC and digital I O 275 ...
Page 276: ...276 ...
Page 282: ...282 CMOD 02 multifunction extension module external 24 V AC DC and isolated PTC interface ...