Package weight
Frame
size
lb
kg
51.6
23.4
R3
164.9
74.8
R6
299.8
2)
136
1)
R8
1) for types -105A-3, 145A-3, -101A-5, -124A-5: 121 kg
2) for types -105A-3, 145A-3, -101A-5, -124A-5: 266.8 lb
Losses, cooling data and noise
The air flow direction is from bottom to top.
This table shows typical heat loss values, required air flow and noise at the nominal
ratings of the drive. The heat loss values can vary depending on voltage, cable
conditions, motor efficiency and power factor. To obtain more accurate values for
given conditions, use ABB DriveSize tool
(
http://new.abb.com/drives/software-tools/drivesize
).
IEC
Frame
Noise
Air flow
Heat dissipation
ACH580-
31-…
Main cir-
cuit and
control
boards
Control
circuit
maxim-
um
Control
circuit
minim-
um
Main cir-
cuit at
rated
I1
at
I2
dB(A)
ft3/min
m3/h
W
W
W
W
Un = 400 V
R3
57
212
361
226
36
4.1
190
09A5-4
R3
57
212
361
329
36
4.1
293
12A7-4
R3
57
212
361
395
36
4.1
359
018A-4
R3
57
212
361
579
36
4.1
543
026A-4
R6
71
324
550
625
36
4.1
589
033A-4
R6
71
324
550
751
36
4.1
715
039A-4
R6
71
324
550
912
36
4.1
876
046A-4
R6
71
324
550
1088
36
4.1
1052
062A-4
R6
71
324
550
1502
36
4.1
1466
073A-4
R6
71
324
550
1904
36
4.1
1868
088A-4
R8
68
860/913
1)
1877
36
4.1
1841
106A-4
R8
68
2963
36
4.1
2927
145A-4
R8
68
3168
36
4.1
3132
169A-4
R8
68
3990
36
4.1
3954
206A-4
Un = 480 V
190 Technical data
Summary of Contents for ACH580-31
Page 1: ... ABB INDUSTRIAL DRIVES ACH580 31 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 30: ...30 ...
Page 39: ...Operation principle 39 ...
Page 56: ...56 ...
Page 90: ...90 ...
Page 112: ...R3 1 7 N m 112 Electrical installation IEC ...
Page 113: ...R6 1 7 N m Electrical installation IEC 113 ...
Page 114: ...R8 1 7 N m 114 Electrical installation IEC ...
Page 130: ...R3 Max 250 mA 130 Electrical installation North America NEC ...
Page 131: ...R6 Electrical installation North America NEC 131 ...
Page 150: ...150 ...
Page 152: ...152 ...
Page 166: ... Fan arrow must point up 166 Maintenance ...
Page 212: ...212 ...
Page 214: ...R3 IP21 UL Type 1 3AXD50000028643 214 Dimension drawings ...
Page 215: ...R3 Option B056 IP55 UL Type 12 3AXD50000045321 Dimension drawings 215 ...
Page 216: ...R6 IP21 UL Type 1 3AXD50000037446 216 Dimension drawings ...
Page 217: ...R6 Option B056 IP55 UL Type 12 3AXD50000045351 Dimension drawings 217 ...
Page 218: ...R8 IP21 UL Type 1 3AXD50000147052 218 Dimension drawings ...
Page 219: ...R8 Option B056 IP55 UL Type 12 3AXD50000147052 Dimension drawings 219 ...
Page 220: ...220 ...
Page 242: ...242 ...
Page 250: ...250 ...
Page 254: ...254 ...
Page 262: ...262 ...
Page 268: ...268 ...
Page 275: ...CMOD 01 multifunction extension module external 24 V AC DC and digital I O 275 ...
Page 276: ...276 ...
Page 282: ...282 CMOD 02 multifunction extension module external 24 V AC DC and isolated PTC interface ...