Activation switch
In the wiring diagrams, the activation switch has the designation [K]. This
represents a component such as a manually operated switch, an emergency stop
push button switch, or the contacts of a safety relay or safety PLC.
•
In case a manually operated activation switch is used, the switch must be of
a type that can be locked out to the open position.
•
The contacts of the switch or relay must open/close within 200 ms of each
other.
•
A CPTC thermistor protection module or an FSPS safety functions module can
also be used. For more information, see the module documentation.
■
Cable types and lengths
•
ABB recommends double-shielded twisted-pair cable.
•
Maximum cable lengths:
•
300 m (1000 ft) between activation switch [K] and drive control unit
•
60 m (200 ft) between multiple drives
•
60 m (200 ft) between external power supply and first control unit
Note: A short-circuit in the wiring between the switch and an STO terminal causes
a dangerous fault. Therefore, it is recommended to use a safety relay (including
wiring diagnostics) or a wiring method (shield grounding, channel separation)
which reduces or eliminates the risk caused by the short-circuit.
Note: The voltage at the STO input terminals of the drive must be at least 13 V DC
to be interpreted as “1”.
The pulse tolerance of the input channels is 1 ms.
■
Grounding of protective shields
•
Ground the shield in the cabling between the activation switch and the control
unit at the control unit only.
•
Ground the shield in the cabling between two control units at one control unit
only.
228 The Safe torque off function
Summary of Contents for ACH580-31
Page 1: ... ABB INDUSTRIAL DRIVES ACH580 31 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 30: ...30 ...
Page 39: ...Operation principle 39 ...
Page 56: ...56 ...
Page 90: ...90 ...
Page 112: ...R3 1 7 N m 112 Electrical installation IEC ...
Page 113: ...R6 1 7 N m Electrical installation IEC 113 ...
Page 114: ...R8 1 7 N m 114 Electrical installation IEC ...
Page 130: ...R3 Max 250 mA 130 Electrical installation North America NEC ...
Page 131: ...R6 Electrical installation North America NEC 131 ...
Page 150: ...150 ...
Page 152: ...152 ...
Page 166: ... Fan arrow must point up 166 Maintenance ...
Page 212: ...212 ...
Page 214: ...R3 IP21 UL Type 1 3AXD50000028643 214 Dimension drawings ...
Page 215: ...R3 Option B056 IP55 UL Type 12 3AXD50000045321 Dimension drawings 215 ...
Page 216: ...R6 IP21 UL Type 1 3AXD50000037446 216 Dimension drawings ...
Page 217: ...R6 Option B056 IP55 UL Type 12 3AXD50000045351 Dimension drawings 217 ...
Page 218: ...R8 IP21 UL Type 1 3AXD50000147052 218 Dimension drawings ...
Page 219: ...R8 Option B056 IP55 UL Type 12 3AXD50000147052 Dimension drawings 219 ...
Page 220: ...220 ...
Page 242: ...242 ...
Page 250: ...250 ...
Page 254: ...254 ...
Page 262: ...262 ...
Page 268: ...268 ...
Page 275: ...CMOD 01 multifunction extension module external 24 V AC DC and digital I O 275 ...
Page 276: ...276 ...
Page 282: ...282 CMOD 02 multifunction extension module external 24 V AC DC and isolated PTC interface ...