340 EMC filters
WARNING!
An EMC filter must not be installed if the drive is connected to
an IT power system (i.e. an ungrounded, or a high resistance grounded
[over 30 ohm] power system) or a corner-grounded TN system.
Selecting EMC filters
Degree of protection
IP20
Dimensions and weights
See dimension drawing of
on page
.
For data of dimensions, wire sizes and tightening torques, see
.
Drive type
ACL30-04...
Frame
Filter type
EN 61800-3: 2004 Category C2
-06A0
B
JFI-02*
-09A0
B
JFI-03*
-013A
-017A
-023A
C
JFI-05*
-030A
-050A
D
JFI-07*
-070A
*External filter; to be ordered separately