50 Planning the electrical installation
Typical power cable sizes
The table below gives copper cable types with concentric copper shield for the drives
with nominal current. The value separated by the plus sign means the diameter of the
PE conductor.
Drive type
ACL30-04...
Frame size
IEC
1)
US
Cu cable type
mm
2)
AWG/kcmil
-06A0
B
3×1.5 +1.5
16
-09A0
B
3×1.5 +1.5
16
-013A
B
3×2.5 +2.5
14
-017A
B
3×4 +4
14
-023A
C
3×10 +10
6
-030A
C
3×10 +10
6
-050A
D
3×10 +10
6
-070A
D
3×10 +10
6
1)
The cable sizing is based on maximum six cables laid on a cable ladder side by side, ambient temperature
30 °C, PVC insulation, surface temperature 70 °C.
For other conditions, size of the cables according to local safety regulations, appropriate input voltage and
load current of the drive, see
2)
Without additional choke
Summary of Contents for ACL30
Page 1: ...ABB high performance elevator drives User s manual ACL30 elevator drive ...
Page 4: ......
Page 20: ...20 Safety instructions ...
Page 34: ...34 Operation principle and hardware description ...
Page 42: ...42 Planning the cabinet installation ...
Page 60: ...60 Planning the electrical installation ...
Page 126: ...126 Using the control panel ...
Page 318: ...318 Maintenance ...
Page 334: ...334 The Safe torque off function ...
Page 338: ...338 Mains chokes ...
Page 342: ...342 EMC filters ...
Page 348: ...Dimension drawings 348 Frame size B D1 D2 W H1 H2 ...
Page 349: ...Dimension drawings 349 ...
Page 350: ...Dimension drawings 350 Frame size C D1 D2 H2 H1 W ...
Page 351: ...Dimension drawings 351 ...
Page 352: ...Dimension drawings 352 Frame size D ...
Page 354: ...354 Dimension drawings EMC filters JFI 0x ...
Page 356: ...356 Dimension drawings Brake resistors JBR xx ...
Page 358: ...358 Dimension drawings ...