188
ACQ550-U1 User’s Manual
Embedded fieldbus
Relay output control
Using the fieldbus for relay output control requires:
•
Drive parameter values set as defined below.
•
Fieldbus controller supplied reference word(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
1. More than 3 relays requires the addition of a relay extension module.
For example:
To control relays 1 and 2 using serial communication:
Set parameters 1401
RELAY
OUTPUT
1 and 1402
RELAY
OUTPUT
1 = 35 (
COMM
).
Note:
Relay status feedback occurs without configuration as defined below.
Drive Parameter
Value
Setting
Protocol Reference
Modbus
BACnet
ABB
DRV
DCU
PROFILE
1401
RELAY
OUTPUT
1
35
(
COMM
)
Relay Output 1
controlled by fieldbus.
40134 bit 0 or 00033
BO0
1402
RELAY
OUTPUT
2
35
(
COMM
)
Relay Output 2
controlled by fieldbus.
40134 bit 1 or 00034
BO1
1403
RELAY
OUTPUT
3
35
(
COMM
)
Relay Output 3
controlled by fieldbus.
40134 bit 2 or 00035
BO2
1410
1
RELAY
OUTPUT
4
35
(
COMM
)
Relay Output 4
controlled by fieldbus.
40134 bit 3 or 00036
BO3
1411
1
RELAY
OUTPUT
5
35
(
COMM
)
Relay Output 5
controlled by fieldbus.
40134 bit 4 or 00037 BO4
1412
1
RELAY
OUTPUT
6
35
(
COMM
)
Relay Output 6
controlled by fieldbus.
40134 bit 5 or 00038
BO5
Drive
Parameter
Value
Setting
Protocol Reference
Modbus
BACnet
ABB
DRV
DCU
PROFILE
0122
RO
1-3
STATUS
Relay 1…3
status.
40122
0122
BI0…
BI2
0123
RO
4-6
STATUS
Relay 4…6
status.
40123
0123
BI3…
BI5
Summary of Contents for ACQ550-U1-011A-6
Page 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 U1 User s Manual Table of contents ...
Page 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Page 56: ...56 ACQ550 U1 User s Manual Control panel ...
Page 68: ...68 ACQ550 U1 User s Manual Application macros ...
Page 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Page 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Page 314: ...314 ACQ550 U1 User s Manual Index ...