BACnet quick-start sequence
The following steps summarize the process for enabling and configuring BACnet on
the ACQ550:
1. Enable BACnet protocol: Set drive parameter 9802,
COMM
PROTOCOL
SEL
=
BACNET
(5).
Note:
If you cannot see the desired selection on the panel, your drive does not have
that protocol software in the application memory.
•
To confirm this selection, read drive parameter 5301,
EFB
PROTOCOL
ID
. It should
read x5xx (where “x” is any value).
2. Place the BACnet channel in “reset”: Set drive parameter 5302,
EFB
STATION
ID
= 0.
•
This setting holds the BACnet communication channel in reset while remaining
settings are completed.
3. Define the MS/TP baud rate.
•
Set drive parameter 5303,
EFB
BAUD
RATE
= appropriate value.
4. Define the Device Object Instance ID.
•
To define a specific device object instance value, use drive parameters 5311 and
5317 (object instance values must be unique and in the range 1 to 4,194,303).
•
To use the drive’s MS/TP MAC ID as the device object instance value, set drive
parameter 5311 and 5317 = 0.
•
BACnet requires a unique Device Object ID for each device on the BACnet
network.
5. Define a unique MS/TP MAC ID. Set drive parameter 5302,
EFB
STATION
ID
=
appropriate value.
•
Once this parameter is set to a non-zero value, current BACnet settings are
“latched” and used for communication until the channel is reset.
AV26
MBOX DATA
This object holds the mailbox function’s
parameter value – a value that was read,
or is to be written. See BV15 and BV16.
None
W
AV27
EXT PID STPT
This object sets the External PID
controller setpoint. The corresponding
drive parameter is 4211. Control requires
parameter 4210,
PID
SETPOINT
SEL
, value
= 19 (
INTERNAL
).
Percent
C
Instance
ID
Object Name
Description
Units
Present Value
Access Type
Summary of Contents for ACQ550-U1-011A-6
Page 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 U1 User s Manual Table of contents ...
Page 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Page 56: ...56 ACQ550 U1 User s Manual Control panel ...
Page 68: ...68 ACQ550 U1 User s Manual Application macros ...
Page 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Page 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Page 314: ...314 ACQ550 U1 User s Manual Index ...