292
ACQ550-U1 User’s Manual
Technical data
Air flow, 500…600 V drives
The following table lists heat loss and air flow data for 500…600 V drives.
-038A-4
R3
562
1919
134
79
-045A-4
R3
667
2278
280
165
-059A-4
R4
907
3098
280
165
-072A-4
R4
1120
3825
280
165
-078A-4
R4
1295
4423
280
165
-097A-4
R4
1440
4918
250
147
-125A-4
R5
1940
6625
404
238
-157A-4
R6
2310
7889
404
238
-180A-4
R6
2810
9597
404
238
-246A-4
R6
3260
11134
540
318
00467918.xls C
Drive
Heat loss
Air flow
ACQ550-U1-
Frame size
W
BTU/hr
m
3
/h
ft
3
/min
-02A7-6
R2
46
157
88
52
-03A9-6
R2
68
232
88
52
-06A1-6
R2
124
423
88
52
-09A0-6
R2
170
581
88
52
-011A-6
R2
232
792
88
52
-017A-6
R2
337
1150
88
52
-022A-6
R3
457
1560
134
79
-027A-6
R3
562
1918
134
79
-032A-6
R4
667
2276
280
165
-041A-6
R4
907
3096
280
165
-052A-6
R4
1120
6820
280
165
-062A-6
R4
1295
4420
280
165
-077A-6
R6
1504
5136
404
238
-099A-6
R6
1821
6219
404
238
-125A-6
R6
2442
8339
404
238
-144A-6
R6
2813
9607
404
238
00467918.xls C
Drive
Heat loss
Air flow
ACQ550-x1-
Frame size
W
BTU/hr
m
3
/h
ft
3
/min
Summary of Contents for ACQ550-U1-011A-6
Page 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 U1 User s Manual Table of contents ...
Page 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Page 56: ...56 ACQ550 U1 User s Manual Control panel ...
Page 68: ...68 ACQ550 U1 User s Manual Application macros ...
Page 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Page 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Page 314: ...314 ACQ550 U1 User s Manual Index ...