204
ACQ550-U1 User’s Manual
Embedded fieldbus
Actual values
The contents of the register addresses 40005…40012 are
ACTUAL
VALUES
and are:
•
specified using parameters 5310…5317
•
Read-only values containing information on the operation of the drive
•
16-bit words containing a sign bit and a 15-bit integer
•
when negative values, written as the two’s complement of the corresponding
positive value
•
scaled as described earlier in section
on page
.
Exception codes
Exception codes are serial communication responses from the drive. The ACQ550
supports the standard Modbus exception codes defined below.
Exception
code
Name
Meaning
01
ILLEGAL
FUNCTION
Unsupported Command
02
ILLEGAL
DATA
ADDRESS
The data address received in the query is not allowable. It is not
a defined parameter/group.
03
ILLEGAL
DATA
VALUE
A value contained in the query data field is not an allowable
value for the ACQ550, because it is one of the following:
• Outside min. or max. limits.
• Parameter is read-only.
• Message is too long.
• Parameter write not allowed when start is active.
• Parameter write not allowed when factory macro is selected.
Summary of Contents for ACQ550-U1-011A-6
Page 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 U1 User s Manual Table of contents ...
Page 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Page 56: ...56 ACQ550 U1 User s Manual Control panel ...
Page 68: ...68 ACQ550 U1 User s Manual Application macros ...
Page 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Page 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Page 314: ...314 ACQ550 U1 User s Manual Index ...