224
ACQ550-U1 User’s Manual
Embedded fieldbus
•
In order to participate in MS/TP token passing, the MAC ID used must be within
the limits defined by other masters’ “Max Master” property.
6. Confirm proper BACnet communication.
•
When BACnet communication is operating properly, drive parameter 5316,
EFB
PAR
16 (the MS/TP token counter), should be continually increasing.
•
Drive parameter 5306,
UART
ERRORS
, should be stable. (With autobaud detection,
this parameter may increase until the proper baud rate is detected.)
7. Configure the Device Object Name.
•
BACnet requires a unique name for each device on the BACnet network. Write
the Object Name of the Device Object of the drive to a unique text string using the
operator workstation or software tool capable of writing BACnet properties. The
Object Name cannot be modified with the ABB display panel and only the Device
Object name is writable in this product. We do not support writing of Device
Description.
BACnet Device Address Rules
OWS
(Operator
Workstation)
Router 1
Router 2
VAV1
VAV2
VAV3
ACH 550
IP
MSTP
MSTP
MSTP MAC=1
(param 53.02 = 1)
DeviceOID=3001
(param 53.11 = 3001)
(param 53.17 = 0)
MSTPNetwork#=3
MSTP MAC=0
DeviceOID=3000
IP Network#=1
MSTP MAC=1
DeviceOID=2001
MSTP MAC=2
DeviceOID=2002
MSTP MAC=3
DeviceOID=2003
MSTP Network#=2
MSTP MAC=0
DeviceOID=2000
IP Network#=1
-- MSTP MAC Addresses must be unique for all devices connected to the same RS485 network.
-- MSTP MAC Address is configurable via parameter 5302 in ACH550.
1..127 = range of supported Master addresses for ACH550
-- Network Number must be unique for each network (IP and MSTP)
-- Network Number of 0 is reserved for broadcasts
-- Device Object IDs must be unique across the entire BACnet network, all IP and MSTP subnetworks.
-- Device Object IDs are 22 bits, configurable via parameters 5311 and 5317 in ACH550.
-- The example Network Numbers and DeviceOIDs show a good way to maintain unique DeviceOIDs
across the network.
IP Network#=1
Drive 2
Drive 3
MSTP MAC=2
DeviceOID=3002
MSTP MAC=3
DeviceOID=3003
-- MSTP MAC Addresses must be unique for all devices connected to the same RS485 network.
-- MSTP MAC Address is configurable via parameter 5302 in ACQ550.
1..127 = range of supported Master addresses for ACQ550
-- Network Number must be unique for each network (IP and MSTP)
-- Network Number of 0 is reserved for broadcasts
-- Device Object IDs must be unique across the entire BACnet network, all IP and MSTP subnetworks.
-- Device Object IDs are 22 bits, configurable via parameters 5311 and 5317 in ACQ550.
-- The example Network Numbers and DeviceOIDs show a good way to maintain unique Device OIDs
across the network.
Summary of Contents for ACQ550-U1-011A-6
Page 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 U1 User s Manual Table of contents ...
Page 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Page 56: ...56 ACQ550 U1 User s Manual Control panel ...
Page 68: ...68 ACQ550 U1 User s Manual Application macros ...
Page 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Page 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Page 314: ...314 ACQ550 U1 User s Manual Index ...