ACQ550-U1 User’s Manual
273
Technical data
Fuses, 500…600 V drives
Emergency stop devices
The overall design of the installation must include emergency stop devices and any
other safety equipment that may be needed. Pressing STOP on the drive’s control
panel does NOT:
•
generate an emergency stop of the motor
•
separate the drive from dangerous potential.
-125A-4
125
160
150
JJS-150
-157A-4
157
200
160
JJS-200
-180A-4
180
250
200
JJS-250
-246A-4
246
250
250
JJS-250
00467918.xls C
ACQ550-U1-
see below
Input current
A
Input power (mains) fuses
IEC 60269 gG (A)
UL Class T (A)
Bussmann type
-02A7-6
2.7
10
10
JJS-10
-03A9-6
3.9
-06A1-6
6.1
-09A0-6
9.0
16
15
JJS-15
-011A-6
11
-017A-6
17
25
25
JJS-25
-022A-6
22
-027A-6
27
35
40
JJS-40
-032A-6
32
-041A-6
41
50
50
JJS-50
-052A-6
52
60
60
JJS-60
-062A-6
62
80
80
JJS-80
-077A-6
77
100
JJS-100
-099A-6
99
125
150
JJS-150
-125A-6
125
160
175
JJS-175
-144A-6
144
200
200
JJS-200
00467918.xls C
ACQ550-x1-
see below
Input current
A
Input power (mains) fuses
IEC 60269 gG (A)
UL Class T (A)
Bussmann type
Summary of Contents for ACQ550-U1-011A-6
Page 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Page 4: ......
Page 10: ...10 ACS550 U1 User s Manual Table of contents ...
Page 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Page 56: ...56 ACQ550 U1 User s Manual Control panel ...
Page 68: ...68 ACQ550 U1 User s Manual Application macros ...
Page 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Page 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Page 314: ...314 ACQ550 U1 User s Manual Index ...