Electrical power network specification
ACQ580-07-xxxxx-4 drives: 380…480 VAC 3-phase ±10%. This is indic-
ated in the type designation label as typical input voltage levels
3~400/480 V AC.
Voltage (
U
1)
TN (grounded) and IT (ungrounded) systems
Network type
Maximum allowable prospective short-circuit current is 65 kA when the
input cable is protected with gG type fuses (IEC 60269) having maximum
current rating as follows:
Short-circuit withstand
strength Icc (IEC/EN
61439-1)
• 400 A for frames R6 to R8
• 630 A for frame R9
• 1000 A for R10
• 1250 A for R11
The drive is suitable for use on a circuit capable of delivering not more
than 100,000 rms symmetrical amperes at 480 V maximum when the
input cable is protected with class T fuses.
Short-circuit current
protection (UL 508A)
50/60 Hz. Variation ±5% of nominal frequency.
Frequency (
f
1)
Max. ± 3% of nominal phase to phase input voltage
Imbalance
0.98 (at nominal load)
Fundamental power
factor (cos phi1)
Motor connection data
Asynchronous AC induction motors, permanent magnet synchronous
motors
Motor types
0 to
U
1, 3-phase symmetrical. This is indicated in the type designation
label as typical output voltage level 3 ~ 0...
U
1.
U
max at the field weak-
ening point.
Voltage (
U
2)
0…500 Hz
Frequency (
f
2)
For drives with du/dt filter: 500 Hz
See section
Current
3 kHz (typically)
Switching frequency
300 m (984 ft).
Maximum recommen-
ded motor cable length Longer cables cause a motor voltage decrease which limits the available
motor power. The decrease depends on the motor cable length and
characteristics. Note that a sine filter (optional) at the drive output also
causes a voltage decrease. Contact ABB for more information.
Note:
With motor cables longer than 100 m (328 ft), the EMC Directive
requirements may not be fulfilled.
Technical data 239
Summary of Contents for ACQ580-07
Page 1: ... ABB DRIVES FOR WATER ACQ580 07 Hardware manual ...
Page 2: ......
Page 4: ......
Page 8: ...4 Update notice ...
Page 20: ...16 ...
Page 26: ...Measuring points of frames R6 to R9 are shown below PE L1 L2 L3 22 Safety instructions ...
Page 32: ...28 ...
Page 38: ...34 ...
Page 66: ...62 ...
Page 69: ...Mechanical installation 65 ...
Page 73: ... Mechanical installation 69 ...
Page 75: ...Declaration of Conformity Mechanical installation 71 ...
Page 108: ...104 ...
Page 133: ...Electrical installation 129 ...
Page 142: ...138 ...
Page 156: ...152 ...
Page 162: ...158 ...
Page 171: ...Maintenance 167 ...
Page 177: ...3 4 Maintenance 173 ...
Page 184: ...14 13 15 16 17 Remove the flange 180 Maintenance ...
Page 187: ...3 4 5 6 Remove the mounting plate Maintenance 183 ...
Page 189: ...8 Disconnect the drive module output busbars M12 70 N m 52 lbf ft 7 8 Maintenance 185 ...
Page 193: ...4 5 3 6 Remove the mounting plate Maintenance 189 ...
Page 195: ...8 Disconnect the drive module output busbars M12 70 N m 52 lbf ft 7 8 Maintenance 191 ...
Page 218: ...Frame R6 Input and motor cable terminal dimensions option F289 DET A 214 Technical data ...
Page 233: ...Frame R9 Input and motor cable terminal dimensions option F289 Technical data 229 ...
Page 257: ...13 Dimension drawings Example dimension drawings are shown below Dimension drawings 253 ...
Page 258: ...Frames R6 and R7 IP21 UL Type 1 254 Dimension drawings ...
Page 259: ...Frames R6 and R7 B054 IP42 UL Type 1 Filtered Dimension drawings 255 ...
Page 260: ...Frames R6 and R7 B055 IP54 UL Type 12 256 Dimension drawings ...
Page 261: ...Frames R6 and R7 H351 and H353 top entry and exit Dimension drawings 257 ...
Page 262: ...Frames R6 and R7 F289 258 Dimension drawings ...
Page 263: ...Frames R6 and R7 F289 H351 H353 Dimension drawings 259 ...
Page 264: ...Frames R8 and R9 IP21 UL Type 1 260 Dimension drawings ...
Page 265: ...Frames R8 and R9 B054 IP42 UL Type 1 Filtered Dimension drawings 261 ...
Page 266: ...Frames R8 and R9 B055 IP54 UL Type 12 262 Dimension drawings ...
Page 267: ...Frames R8 and R9 H351 and H353 top entry and exit Dimension drawings 263 ...
Page 268: ...Frames R8 and R9 F289 264 Dimension drawings ...
Page 269: ...Frames R8 and R9 F289 H351 H353 Dimension drawings 265 ...
Page 295: ... Declaration of conformity The Safe torque off function 291 ...
Page 296: ...292 ...
Page 302: ...298 ...
Page 309: ...CMOD 01 multifunction extension module external 24 V AC DC and digital I O 305 ...
Page 310: ...306 ...
Page 316: ...312 CMOD 02 multifunction extension module external 24 V AC DC and isolated PTC interface ...
Page 322: ...318 ...