Parameters 149
Selects the way the motor is stopped when an emergency
stop command is received.
The source of the emergency stop signal is selected by
parameter
.
Ramp stop (Off1)
With the drive running:
• 1 = Normal operation.
• 0 = Normal stop along the standard deceleration ramp
defined for the particular reference type (see section
[page
]). After the drive has stopped, it
can be restarted by removing the emergency stop signal
and switching the start signal from 0 to 1.
With the drive stopped:
• 1 = Starting allowed.
• 0 = Starting not allowed.
0
Coast stop (Off2)
With the drive running:
• 1 = Normal operation.
• 0 = Stop by coasting. The drive can be restarted by
restoring the start interlock signal and switching the start
signal from 0 to 1.
With the drive stopped:
• 1 = Starting allowed.
• 0 = Starting not allowed.
1
Eme ramp stop
(Off3)
With the drive running:
• 1 = Normal operation
• 0 = Stop by ramping along emergency stop ramp defined
by parameter
. After the drive
has stopped, it can be restarted by removing the
emergency stop signal and switching the start signal from
0 to 1.
With the drive stopped:
• 1 = Starting allowed
• 0 = Starting not allowed
2
Selects the source of the emergency stop signal. The stop
mode is selected by parameter
.
0 = Emergency stop active
1 = Normal operation
Note:
This parameter cannot be changed while the drive is
running.
Active (false)
0.
0
Inactive (true)
1.
1
Reserved
2
DI1
Digital input DI1 (
, bit 0).
3
DI2
Digital input DI2 (
, bit 1).
4
DI3
Digital input DI3 (
, bit 2).
5
DI4
Digital input DI4 (
, bit 3).
6
DI5
Digital input DI5 (
, bit 4).
7
DI6
Digital input DI6 (
, bit 5).
8
). -
No.
Name/Value
Description
Def/FbEq16
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...