Parameters 211
Warning/Fault
The drive generates a warning (
) if the signal stays continuously below the underload
curve for half of the time defined by parameter
The drive trips on
if the signal stays
continuously above the underload curve for a time defined by
parameter
3
Defines the first of the five speed points on the X-axis of the
user load curve.
Speed points are used if parameter
is set to
or if
is set to
and the reference unit is rpm.
The five points must be in order from lowest to highest. The
points are defined as positive values, but the range is
symmetrically effective also in the negative direction. The
monitoring is not active outside these two areas.
150.0 rpm
-30000.0…30000.0
rpm
Speed.
1 = 1 rpm
Defines the second speed point.
See parameter
.
750.0 rpm
-30000.0…30000.0
rpm
Speed.
1 = 1 rpm
Defines the third speed point.
See parameter
.
1290.0 rpm
-30000.0…30000.0
rpm
Speed.
1 = 1 rpm
Defines the fourth speed point.
See parameter
.
1500.0 rpm
-30000.0…30000.0
rpm
Speed.
1 = 1 rpm
Defines the fifth speed point.
See parameter
.
1800.0 rpm
-30000.0…30000.0
rpm
Speed.
1 = 1 rpm
Defines the first of the five frequency points on the X-axis of
the user load curve.
Frequency points are used if parameter
is set to
and the reference unit is Hz.
The five points must be in order from lowest to highest. The
points are defined as positive values, but the range is
symmetrically effective also in the negative direction. The
monitoring is not active outside these two areas.
5.0 Hz
-500.0…500.0 Hz
Frequency.
1 = 1 Hz
Defines the second frequency point.
See parameter
.
25.0 Hz
-500.0…500.0 Hz
Frequency.
1 = 1 Hz
Defines the third frequency point.
See parameter
.
43.0 Hz
-500.0…500.0 Hz
Frequency.
1 = 1 Hz
No.
Name/Value
Description
Def/FbEq16
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...