224 Parameters
Defines the wake-up level as deviation between process
setpoint and feedback.
When the deviation exceeds the value of this parameter, and
remains there for the duration of the wake-up delay (
), the drive wakes up.
See also parameter
.
0.00 PID
customer
units
-200000.00…
200000.00 PID
customer units
Wake-up level (as deviation between process setpoint and
feedback).
1 = 1 PID
customer unit
Defines a wake-up delay for the sleep function to prevent
nuisance wake-ups. See parameter
The delay timer starts when the deviation exceeds the wake-
up level (
), and resets if the
deviation falls below the wake-up level.
0.50 s
0.00…60.00 s
Wake-up delay.
1 = 1 s
Activates (or selects a source that activates) tracking mode.
In tracking mode, the value selected by parameter
is substituted for the PID controller
1 = Tracking mode enabled
Not selected
0.
0
Selected
1.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
Reserved
8…17
Timed function 1
18
Timed function 2
(see page
19
Timed function 3
(see page
20
Supervision 1
21
Supervision 2
22
Supervision 3
23
Source selection (see
). -
Selects the value source for tracking mode. See parameter
Not selected
None.
0
AI1 scaled
).
1
AI2 scaled
).
2
FB A ref1
(see page
3
FB A ref2
(see page
4
Source selection (see
). -
No.
Name/Value
Description
Def/FbEq16
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...