236 Parameters
Total energy consumption during the previous month, that is,
between midnight of the first day or the previous month and
midnight of the first day of the present month.
0.00 kWh
-1000000.00 …
1000000.00 kWh
0.01 = 1 kWh
Value of the peak power over the drive lifetime.
0.00 kW
-3000.00 …
3000.00 kW
Peak power value.
10 = 1 kW
Date of the peak power over the drive lifetime.
1.1.1980
Date.
N/A
Time of the peak power over the drive lifetime.
00:00:00
Time,
N/A
46
46 Monitoring/scaling
settings
Speed supervision settings; actual signal filtering; general
scaling settings.
Defines the maximum speed value used to define the
acceleration ramp rate and the initial speed value used to
define the deceleration ramp rate (see parameter group
). The speed acceleration and
deceleration ramp times are therefore related to this value
(
not
Also defines the 16-bit scaling of speed-related parameters.
The value of this parameter corresponds to 20000 in eg.
fieldbus communication.
1500.00 rpm;
1800.00 rpm
(
0.10…30000.00
rpm
Acceleration/deceleration terminal/initial speed.
1 = 1 rpm
Defines the maximum frequency value used to define the
acceleration ramp rate and the initial frequency value used to
define deceleration ramp rate (see parameter group
). The frequency acceleration and
deceleration ramp times are therefore related to this value
(
not
Also defines the 16-bit scaling of frequency-related
parameters. The value of this parameter corresponds to
20000 in eg. fieldbus communication.
50.00 Hz;
60.00 Hz
(
0.10…1000.00 Hz
Acceleration/deceleration terminal/initial frequency.
10 = 1 Hz
Defines the 16-bit scaling of torque parameters. The value of
this parameter (in percent of nominal motor torque)
corresponds to 10000 in eg. fieldbus communication.
100.0%
0.1…1000.0%
Torque corresponding to 10000 on fieldbus.
10 = 1%
Defines the output power value that corresponds to 10000 in
eg. fieldbus communication. The unit is selected by
parameter
.
1000.00 kW
or hp
0.10 …30000.00
kW or
0.10 …40200.00 hp
Power corresponding to 10000 on fieldbus.
1 = 1 unit
No.
Name/Value
Description
Def/FbEq16
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...