Parameters 269
80
80 Flow calculation and
protection
Actual flow calculation.
Note:
Parameters are dynamically hidden based on selection
of flow calculation mode. Parameters are visible according to
the selection of parameter
Actual system flow that is either calculated from the pressure
difference, measured directly or estimated from the pump
curves.
The calculation method is selected with parameter
See the control chain diagram on page
-
-200000.00…
200000.00 m
3
/h
Calculated flow.
1 = 1 m
3
/h
Shows the percentage of parameter
from
.
0.00
-100.00…100.00%
Flow percentage.
100 = 1%
Shows cumulative calculated flow.
0.00
0.00...
21474836.00 m
3
Total calculated flow.
1 = 1 m
3
Shows the ratio of pump flow rate and power input.
0.00
0.00...
32767.95 m
3
/kWh
Specific energy of the pump.
1 = 1 m
3
/kWh
Shows the estimated head produced by the pump.
0.00
0.00...32767.00 m
Estimated pump head.
1 = 1 m
Selects the source for the flow feedback 1.
Not selected
Feedback not used.
0
AI1 scaled
(see page
).
1
AI2 scaled
(see page
).
2
Freq in scaled
(see page
).
3
AI1 percent
8
AI2 percent
9
Feedback data
storage
10
Selects the source for the flow feedback 2.
Not selected
Feedback not used.
0
AI1 scaled
(see page
).
1
AI2 scaled
(see page
).
2
Freq in scaled
(see page
).
3
AI1 percent
8
AI2 percent
9
Feedback data
storage
10
No.
Name/Value
Description
Def/FbEq16
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...