Parameters 281
Contains hardware-related settings that can be enabled and
disabled by toggling the specific bits.
Note:
The installation of the hardware specified by this
parameter may require derating of drive output, or impose
other limitations. Refer to the hardware manual of the drive.
00000000h…
FFFFFFFFh
Hardware options configuration word.
1 = 1
Specifies hardware-related options that require differentiated
parameter defaults.
This parameter is not affected by a parameter restore.
0000h…FFFFh
Hardware options configuration word.
1 = 1
96
Language selection; access levels; macro selection;
parameter save and restore; control unit reboot; user
parameter sets; unit selection.
Selects the language of the parameter interface and other
displayed information when viewed on the control panel.
Notes:
• Not all languages listed below are necessarily supported.
• This parameter does not affect the languages visible in the
Drive composer PC tool. (Those are specified under
View
-
Settings
-
Drive default language
.)
Not selected
None.
0
English
English.
1033
Deutsch
German.
1031
Italiano
Italian.
1040
Español
Spanish.
3082
Français
French.
1036
Suomi
Finnish.
1035
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Information
0
EX motor
1
ABB Sine filter
1 = An ABB sine filter is connected to the output of the drive.
2…15
Reserved
Bit
Name
Value
0
Supply frequency
60 Hz
Differences in the default values between 50 Hz and
60 Hz supply frequency settings
.
0 = 50 Hz.
1 = 60 Hz.
1…12
Reserved
12
du/dt filter
activation
When active, an external du/dt filter is connected to the drive/inverter
output. The setting will limit the output switching frequency, and
force the fan of the drive/inverter module to full speed.
0 = du/dt filter inactive.
1 = du/dt filter active.
14…15 Reserved
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...