282 Parameters
Svenska
Swedish.
1053
Russki
Russian.
1049
Cesky
Czech.
1029
Pass codes can be entered into this parameter to activate
further access levels (see parameter
) or to configure the user lock.
Entering “358” toggles the parameter lock, which prevents the
changing of all other parameters through the control panel or
the Drive composer PC tool.
Entering the user pass code (by default, “10000000”) enables
parameters
…
, which can be used to define a
new user pass code and to select the actions that are to be
prevented.
Entering an invalid pass code will close the user lock if open,
ie. hide parameters
…
. After entering the code,
check that the parameters are in fact hidden. If they are not,
enter another (random) pass code.
Note:
You must change the default user pass code to
maintain a high level of cybersecurity. Store the code in a safe
place – the protection cannot be disabled even by ABB if the
code is lost.
See also section
(page
).
0…99999999
Pass code.
-
Shows which access levels have been activated by pass
codes entered into parameter
.
0001b
00000000h…
FFFFFFFFh
Active access levels.
-
Restores the original settings of the control program, ie.
parameter default values.
Note:
This parameter cannot be changed while the drive is
running.
Done
Restoring is completed.
0
No.
Name/Value
Description
Def/FbEq16
Bit
Name
0
End user
1
Service
2
Advanced programmer
3…10
Reserved
11
OEM access level 1
12
OEM access level 2
13
OEM access level 3
14
Parameter lock
15
Reserved
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...