Parameters 285
, selects the user parameter set together with
parameter
as follows:
Not selected
0.
0
Selected
1.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
Reserved
8…17
Timed function 1
Bit 0 of
18
Timed function 2
Bit 1 of
19
Timed function 3
Bit 2 of
20
Reserved
21…23
Supervision 1
Bit 0 of
(see page
24
Supervision 2
Bit 1 of
(see page
25
Supervision 3
Bit 2 of
(see page
26
). -
See parameter
No.
Name/Value
Description
Def/FbEq16
Status of source
defined by par.
Status of source
defined by par.
User parameter
set selected
0
0
Set 1
1
0
Set 2
0
1
Set 3
1
1
Set 4
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...