Parameters 287
(Visible when user lock is open)
Selects the actions or functionalities to be prevented by the
user lock. Note that the changes made take effect only when
the user lock is closed. See parameter
Note:
We recommend you select all the actions and
functionalities unless otherwise required by the application.
0000h
0000h…FFFFh
Selection of actions to be prevented by user lock.
-
97
Switching frequency; slip gain; voltage reserve; flux braking;
anti-cogging (signal injection); IR compensation.
Defines the switching frequency of the drive that is used as
long as the drive stays below the thermal limit. See section
on page
.
Higher switching frequency results in lower acoustic motor
noise. Lower switching frequency generates less switching
losses and reduce EMC emissions.
Note:
If you have a multimotor system, contact your local
ABB representative.
2 kHz
2 kHz.
2
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Information
0
Disable ABB access
levels
1 = ABB access levels (service, advanced programmer, etc.; see
) disabled
1
Freeze parameter
lock state
1 = Changing the parameter lock state prevented, ie. pass code
358 has no effect
2
Disable file
download
1 = Loading of files to drive prevented. This applies to
• firmware upgrades
• parameter restore
• loading an adaptive program
• changing home view of control panel
• editing drive texts
• editing the favorite parameters list on control panel
• configuration settings made through control panel such as
time/date formats and enabling/disabling clock display.
3…10
Reserved
11
Disable OEM access
level 1
1 = OEM access level 1 disabled
12
Disable OEM access
level 2
1 = OEM access level 2 disabled
13
Disable OEM access
level 3
1 = OEM access level 3 disabled
14…15 Reserved
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...