298 Parameters
Differences in the default values between 50 Hz and 60 Hz
supply frequency settings
Parameter
changes the drive
parameter default values according to the supply frequency, 50 Hz or 60 Hz. The bit
is set according to the market before the drive is delivered.
If you need to change from 50 Hz to 60 Hz, or vice versa, change the value of the bit
and then do a complete reset to the drive. After that you have to reselect the macro to
be used.
The table below shows the parameters whose default values depend on the supply
frequency setting. The supply frequency setting, with the type designation of the
drive, also affects Group
parameter values though these parameters
are not listed in the table.
No
Name
bit
50 Hz
bit
60 Hz
1500.000
1800.000
1500.000
1800.000
50.000
60.000
50.0
60.0
300.00 rpm
360.00 rpm
600.00 rpm
720.00 rpm
900 .00 rpm
1080.00 rpm
1200.00 rpm
1440.00 rpm
1500.00 rpm
1800.00 rpm
2400.00 rpm
2880.00 rpm
3000.00 rpm
3600.00 rpm
5.00 Hz
6.00 Hz
10.00 Hz
12.00 Hz
15.00 Hz
18.00 Hz
20.00 Hz
24.00 Hz
25.00 Hz
30.00 Hz
40.00 Hz
48.00 Hz
50.00 Hz
60.00 Hz