Parameters 159
Defines constant speed 5.
1500.00 rpm;
1800.00 rpm
(
b0)
-30000.00…
30000.00 rpm
Constant speed 5.
See par.
Defines constant speed 6.
2400.00 rpm;
2880.00 rpm
(
b0)
-30000.00…
30000.00 rpm
Constant speed 6.
See par.
Defines constant speed 7.
3000.00 rpm;
3600.00 rpm
(
b0)
-30000.00…
30000.00 rpm
Constant speed 7.
See par.
Defines a safe speed reference value that is used with
supervision functions such as
•
•
•
0.00 rpm
-30000.00…
30000.00 rpm
Safe speed reference.
See par.
Enables/disables the critical speeds function. Also
determines whether the specified ranges are effective in both
rotating directions or not.
See also section
(page
).
0000b
0000b…0011b
Critical speeds configuration word.
1 = 1
Defines the low limit for critical speed range 1.
Note:
This value must be less than or equal to the value of
.
0.00 rpm
-30000.00…
30000.00 rpm
Low limit for critical speed 1.
See par.
Defines the high limit for critical speed range 1.
Note:
This value must be greater than or equal to the value of
.
0.00 rpm
-30000.00…
30000.00 rpm
High limit for critical speed 1.
See par.
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Information
0
Enable
1 = Enable: Critical speeds enabled.
0 = Disable: Critical speeds disabled.
1
Sign mode
1 = Signed: The signs of parameters
are taken into
account.
0 = Absolute: Parameters
are handled as absolute values.
Each range is effective in both directions of rotation.
2…15
Reserved
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...