Parameters 233
Monetary savings compared to direct-on-line motor
connection. This value is a calculated by multiplying the
saved energy in kWh by the currently active energy tariff
(
).
If you have not set the currency during the first start-up, you
can specify it in
Main menu - Primary settings - Clock,
region display - Units - Currency
.
This parameter is read-only (see parameter
).
-
0.00…
21474830.08 units
Monetary savings.
1 = 1 unit
Reduction in CO
2
emissions in metric kilotons compared to
direct-on-line motor connection. This value is incremented
when parameter
rolls over.
This parameter is read-only (see parameter
).
-
0…65535 metric
kilotons
Reduction in CO
2
emissions in metric kilotons.
1 = 1 metric
kiloton
Reduction in CO
2
emissions in metric tons compared to
direct-on-line motor connection. This value is calculated by
multiplying the saved energy in MWh by the value of
parameter
(by default, 0.5
metric tons/MWh).
When this parameter rolls over, parameter
is incremented.
This parameter is read-only (see parameter
).
-
0.0…999.9 metric
tons
Reduction in CO
2
emissions in metric tons.
1 = 1 metric
ton
Reduction in CO
2
emissions in metric tons compared to
direct-on-line motor connection. This value is calculated by
multiplying the saved energy in MWh by the value of
parameter
(by default, 0.5
metric tons/MWh).
This parameter is read-only (see parameter
).
-
0.0…214748300.8
metric tons
Reduction in CO
2
emissions in metric tons.
1 = 1 metric
ton
Enables/disables the energy optimization function. The
function optimizes the motor flux so that total energy
consumption and motor noise level are reduced when the
drive operates below the nominal load. The total efficiency
(motor and drive) can be improved by 1…20% depending on
load torque and speed.
Note:
With a permanent magnet motor and a synchronous
reluctance motor, energy optimization is always enabled
regardless of this parameter.
Disable
Energy optimization disabled.
0
Enable
Energy optimization enabled.
1
No.
Name/Value
Description
Def/FbEq16
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...