276 Parameters
Fault
fault.
2
Defines the delay time at which setpoint must be reached
after last change in PID reference ramp output.
60.0
0.0...1800.0 s
Time-out limit in seconds.
1 = 1 s
Outlet minimum
pressure protection
Enables outlet minimum pressure protection function.
Disabled
Outlet minimum pressure protection function is disabled.
0
Warning
Outlet minimum pressure protection function generates
warning when the outlet minimum
pressure is below the level defined with parameter
Outlet minimum pressure warning level
1
Fault
Outlet minimum pressure protection function generates
fault when the outlet minimum
pressure is below the level defined with parameter
Outlet minimum pressure fault level
for a time set in
.
2
Warning/Fault
Outlet minimum pressure protection function first generates a
warning when the pressure is below the level defined with
parameter
Outlet minimum pressure warning level
for a
time set in parameter
.
If the pressure continues to fall below the level defined with
parameter
Outlet minimum pressure fault level
, outlet
minimum pressure fault is generated.
3
Outlet minimum
pressure warning
level
Defines the level at which drive should generate the outlet
minimum pressure warning.
0.00
0.00...32767.00 bar Outlet minimum pressure warning level.
1 = 1 bar
Outlet minimum
pressure fault level
Defines the level at which drive should generate the outlet
minimum pressure fault.
0.00
0.00...32767.00 bar Outlet minimum pressure fault level.
1 = 1 bar
Outlet maximum
pressure protection
Enables outlet maximum pressure protection function.
Disabled
Outlet maximum pressure protection is disabled.
0
Warning
Outlet maximum pressure protection function generates
warning when the pressure
is above the level defined with parameter
maximum pressure warning level
1
Fault
Outlet maximum pressure protection function generates
fault when the pressure is above
the level defined with parameter
for a time set in parameter
2
Warning/Fault
Outlet maximum pressure protection function first generates
a warning when the pressure is above the level defined with
parameter
Outlet maximum pressure warning level
for
a time set in parameter
If the pressure raises above the level defined with parameter
Outlet maximum pressure fault level
, outlet maximum
pressure fault is generated.
3
No.
Name/Value
Description
Def/FbEq16
Summary of Contents for ACQ580
Page 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Page 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Page 30: ...26 Start up control with I O and ID run ...
Page 40: ...36 Default configuration ...
Page 304: ...300 Parameters ...
Page 340: ...336 Additional parameter data ...