Terminal sizes
• Frame sizes R0…R8: 0.14…1.5 mm
2
(all terminals)
• Tightening torques: 0.5…0.6 N·m (0.4 lbf·ft)
Notes
1)
Current [0(4)…20 mA,
R
in
< 500 ohm] or voltage [ 0(2)…10 V,
R
in
> 200 kohm]
input as selected with parameter
12.15 AI1 unit selection
.
2)
Current [0(4)…20 mA,
R
in
= 100 ohm] or voltage [ 0(2)…10 V,
R
in
> 200 kohm]
input as selected with parameter
12.25 AI2 unit selection
.
3)
Total load capacity of the auxiliary voltage 24V (X2:10) =
6.0 W (250 mA / 24 V) - User can use this source for either of the I/O connections
(DI1... DI2- RO1 or DI3...DI6 - RO2~RO3).
4)
Connected with jumpers at the factory.
5)
Applicable for R0~R2 frames only.
6)
Use shielded twisted-pair cables for digital signals.
7)
Ground the outer shield of the cable 360 degrees under the grounding clamp on
the grounding shelf for the control cables.
8)
Input signal
9)
Output signal
For information on cable connection and drive operation, see
Control Connections
in
the hardware manual (3AXD50000170661).