5093
Rating ID mismatch
Mismatch of drive hardware and
memory information.
Cycle power to the drive. You may
have to be repeat this.
5094
Measurement circuit
temperature
Fault in internal temperature
measurement.
Contact ABB.
5095
Redundant
measurement
Duplicated measurements are
beyond limits.
Contact ABB.
5096
Overtemperature hw
Excessive hardware temperature.
Contact your local ABB
representative.
5098
I/O communication
loss
Communication failure to standard
I/O.
Try resetting the fault or cycle the
power to the drive.
5681
PU communication
Communication errors between drive
control unit and power unit.
Check connections and parameter
5682
Power unit lost
Connection lost between drive
control unit and power unit.
Check connections.
5690
PU communication
internal
Internal communication error.
Contact ABB.
5691
Measurement circuit
ADC
Measurement circuit fault.
Contact ABB.
5692
PU board powerfail
Power unit power supply failure.
Contact ABB.
5693
Measurement circuit
DFF
Measurement circuit fault.
Contact ABB.
5695
Reduced run
Configured power units not found.
Configure the power units.
5696
PU state feedback
State feedback from output phases
does not match control signals.
Contact ABB.
5697
Charging feedback
Charging feedback signal missing.
Check feedback signal from charging
system
5698
Unknown PU fault
The power unit logic generated a
fault which is not known by software.
Check the logic and software
compatibility.
50A0
Fan
Cooling fan stuck or disconnected.
Check fan operation and connection.
Replace fan if faulty.
6181
FPGA version
incompatible
Firmware and FPGA versions are
incompatible.
Reboot the control unit with
parameter
or by cycling power. If the problem
persists, contact ABB.
6306
FBA A mapping file
Fieldbus adapter A mapping file read
error.
Contact ABB.
6481
Task overload
Internal fault.
Note
: This fault cannot be reset.
Reboot the control unit using
parameter
or by cycling power. If the problem
persists, contact ABB.
6487
Stack overflow
Internal fault.
Reboot the control unit. If the problem
persists, contact ABB.
64A1
Internal file load
File read error.
Reboot the control unit. If the problem
persists, contact ABB.
64A3
Application loading
Application file incompatible or
corrupted.
Check the auxiliary code. See actions
for each code below.
8006 Not enough memory for the
application.
Reduce the size of the application.
Reduce the number of parameter
mappings.
See the drive-specific log generated
by Automation Builder.
Code
(hex)
Fault / Aux. code
aux
code visible only on
assistant control panel
and drive composer
)
Cause
What to do